Default settings and ranges (viewed in mate3), Specifications – Outback Power Systems GFX International Series Operators Manual User Manual
Page 52
Specifications
50
900-0112-01-00 Rev B
Default Settings and Ranges (viewed in MATE3)
Table 20
12-Volt Inverter Settings (MATE3)
Field Item Default
Minimum
Maximum
Sensitivity (see page 14 for increments)
6 0 50
Pulse Length
8 4 20
Search
Pulse Spacing
60 AC cycles
4 AC cycles
120 AC cycles
Input Type
Grid
Grid or Gen
Input Support
Y
Y or N
Grid Input AC Limit
25 Aac
2.5 Aac
30 Aac
Gen Input AC Limit
25 Aac
2.5 Aac
30 Aac
AC Input and
Current Limit
Charger AC Limit
5 Aac
0 Aac
6 Aac
LowerVoltage Limit
208 Vac
140 Vac
220 Vac
Upper Voltage Limit
252 Vac
250 Vac
280 Vac
Grid AC Input
Voltage Limits
Transfer Delay
6 AC cycles
0 AC cycles
240 AC cycles
LowerVoltage Limit
208 Vac
140 Vac
220 Vac
Upper Voltage Limit
252 Vac
250 Vac
280 Vac
Transfer Delay
6 AC cycles
0 AC cycles
240 AC cycles
Gen AC Input
Voltage Limits
Connect Delay
0.5 minutes
0.2 minutes
15 minutes
AC Output
AC Output
230 Vac
210 Vac
250 Vac
Cut-Out Voltage
10.5 Vdc
9 Vdc
12 Vdc
Low Battery
Cut-In Voltage
12.5 Vdc
10 Vdc
14 Vdc
Absorb Voltage
14.4 Vdc
13 Vdc
16 Vdc
(Absorb) Time
1.0 hours
0.0 hours
24.0 hours
Float Voltage
13.6 Vdc
12 Vdc
15 Vdc
(Float) Time
1.0 hours
0.0 hours
24.0 hours
Battery Charger
Re-Float Voltage
12.5 Vdc
12 Vdc
13 Vdc
Equalize Voltage
14.6 Vdc
14 Vdc
17 Vdc
Battery Equalize
(Equalize) Time
1.0 hours
0.0 hours
24.0 hours
Aux Mode
Cool Fan
Remote, Load Shed, Gen Alert, Fault, Vent Fan,
Cool Fan, Divert DC, Divert AC, or AC Drop
(Load Shed) Enable Voltage
11 Vdc
10 Vdc
14 Vdc
(Gen Alert) ON Voltage
11 Vdc
10 Vdc
14 Vdc
(Gen Alert ON) Delay
4 minutes
0 minutes
240 minutes
(Gen Alert) OFF Voltage
14 Vdc
12 Vdc
18 Vdc
(Gen Alert OFF) Delay
9 minutes
0 minutes
240 minutes
(Vent Fan) Enable Voltage
13 Vdc
10 Vdc
16 Vdc
(Vent Fan) Off Period
5 minutes
0 minutes
30 minutes
(Divert DC or AC) Enable Voltage
14.6 Vdc
12 Vdc
16 Vdc
Auxiliary
Output
(Divert DC or AC) Off Delay
30 seconds
0 seconds
240 seconds
Inverter Stacking
Stack Mode
Master
Master, OB Slave L1, 3p Classic B , 3p Classic C
Master Adjust Only
0 0 7
Power Save
Slave Adjust Only
1 1 15
Grid Tie Enable
Y
Y or N
Sell Voltage
13 Vdc
10 Vdc
15 Vdc
Grid-Tie Sell
Grid Tie Window
IEEE
IEEE or user
Input Voltage
7
-1 -3 1
Output Voltage
7
-1 -3 1
Calibrate
Battery Voltage
8
0.0 -0.2 0.2
7
These values represent an adjustable setting with a total range of 4 Vac. The default value of -1 means the calibration will subtract 1 volt from the measured
value. The range of settings allow up to 1 volt to be added to the measured value, or up to 3 volts to be subtracted from it. The result is also displayed.
8
These values represent an adjustable setting with a range of ± 0.2 Vdc from the measured value. The range of settings allow up to 0.2 volts to be either
added or subtracted from the measured value. The result is also displayed.