Default settings and ranges (viewed in mate3), Specifications – Outback Power Systems GFX International Series Operators Manual User Manual

Page 52

background image

Specifications

50

900-0112-01-00 Rev B

Default Settings and Ranges (viewed in MATE3)

Table 20

12-Volt Inverter Settings (MATE3)

Field Item Default

Minimum

Maximum

Sensitivity (see page 14 for increments)

6 0 50

Pulse Length

8 4 20

Search

Pulse Spacing

60 AC cycles

4 AC cycles

120 AC cycles

Input Type

Grid

Grid or Gen

Input Support

Y

Y or N

Grid Input AC Limit

25 Aac

2.5 Aac

30 Aac

Gen Input AC Limit

25 Aac

2.5 Aac

30 Aac

AC Input and
Current Limit

Charger AC Limit

5 Aac

0 Aac

6 Aac

LowerVoltage Limit

208 Vac

140 Vac

220 Vac

Upper Voltage Limit

252 Vac

250 Vac

280 Vac

Grid AC Input
Voltage Limits

Transfer Delay

6 AC cycles

0 AC cycles

240 AC cycles

LowerVoltage Limit

208 Vac

140 Vac

220 Vac

Upper Voltage Limit

252 Vac

250 Vac

280 Vac

Transfer Delay

6 AC cycles

0 AC cycles

240 AC cycles

Gen AC Input
Voltage Limits

Connect Delay

0.5 minutes

0.2 minutes

15 minutes

AC Output

AC Output

230 Vac

210 Vac

250 Vac

Cut-Out Voltage

10.5 Vdc

9 Vdc

12 Vdc

Low Battery

Cut-In Voltage

12.5 Vdc

10 Vdc

14 Vdc

Absorb Voltage

14.4 Vdc

13 Vdc

16 Vdc

(Absorb) Time

1.0 hours

0.0 hours

24.0 hours

Float Voltage

13.6 Vdc

12 Vdc

15 Vdc

(Float) Time

1.0 hours

0.0 hours

24.0 hours

Battery Charger

Re-Float Voltage

12.5 Vdc

12 Vdc

13 Vdc

Equalize Voltage

14.6 Vdc

14 Vdc

17 Vdc

Battery Equalize

(Equalize) Time

1.0 hours

0.0 hours

24.0 hours

Aux Mode

Cool Fan

Remote, Load Shed, Gen Alert, Fault, Vent Fan,

Cool Fan, Divert DC, Divert AC, or AC Drop

(Load Shed) Enable Voltage

11 Vdc

10 Vdc

14 Vdc

(Gen Alert) ON Voltage

11 Vdc

10 Vdc

14 Vdc

(Gen Alert ON) Delay

4 minutes

0 minutes

240 minutes

(Gen Alert) OFF Voltage

14 Vdc

12 Vdc

18 Vdc

(Gen Alert OFF) Delay

9 minutes

0 minutes

240 minutes

(Vent Fan) Enable Voltage

13 Vdc

10 Vdc

16 Vdc

(Vent Fan) Off Period

5 minutes

0 minutes

30 minutes

(Divert DC or AC) Enable Voltage

14.6 Vdc

12 Vdc

16 Vdc

Auxiliary
Output

(Divert DC or AC) Off Delay

30 seconds

0 seconds

240 seconds

Inverter Stacking

Stack Mode

Master

Master, OB Slave L1, 3p Classic B , 3p Classic C

Master Adjust Only

0 0 7

Power Save

Slave Adjust Only

1 1 15

Grid Tie Enable

Y

Y or N

Sell Voltage

13 Vdc

10 Vdc

15 Vdc

Grid-Tie Sell

Grid Tie Window

IEEE

IEEE or user

Input Voltage

7

-1 -3 1

Output Voltage

7

-1 -3 1

Calibrate

Battery Voltage

8

0.0 -0.2 0.2

7

These values represent an adjustable setting with a total range of 4 Vac. The default value of -1 means the calibration will subtract 1 volt from the measured

value. The range of settings allow up to 1 volt to be added to the measured value, or up to 3 volts to be subtracted from it. The result is also displayed.

8

These values represent an adjustable setting with a range of ± 0.2 Vdc from the measured value. The range of settings allow up to 0.2 volts to be either
added or subtracted from the measured value. The result is also displayed.