beautypg.com

Environmental specifications, Regulatory specifications, Grid-interactive use – Outback Power Systems GFX International Series Operators Manual User Manual

Page 48: Specifications

background image

Specifications

46

900-0112-01-00 Rev B

Environmental Specifications

Table 15 Environmental Specifications for All Models

Specification Value

Rated Temperature Range (meets all specifications)

0°C to 50°C
(32°F to 122°F)

Operational Temperature Range (functions, but does not necessarily meet all specifications)

–40°C to 60°C
(–40°F to 140 °F )

Storage Temperature Range

–40°C to 60°C
(–40°F to 140°F )

Regulatory Specifications

The International Series GFX inverters are CE compliant for off-grid use.

Grid-Interactive Use

Inverters intended for grid-interactive use must comply with established local standards which
provide regulation for acceptable output voltage ranges, acceptable output frequency, total harmonic
distortion (THD) and anti-islanding performance when the inverter is exporting power to a
utility source.

The OutBack grid-interactive models are validated through compliance testing. The following
specifications refer to exporting power to a simulated utility source of less than 1% voltage total
harmonic distortion (THD).

¾ The THD of the root mean square (RMS) current is less than 5%.
¾ The output of the GFX inverter exceeds the minimum power factor of 0.85 with a typical power factor of 0.96

or better.

¾ All International Series GFX inverters are tested to comply with Table 16.

Table 16 Interconnection Response to Voltage and Frequency

Voltage Range

(AC Volts)

Frequency (Hz)

Allowed Time

(Seconds)

Measured Time

(Seconds)

V < 115

50

0.16

0.020

115 ≤ V < 202.4

50

2.00

0.155

202.4 to 253

50

No interruption

No interruption

253 < V < 276

50

1.00

0.157

V ≥ 276

50

0.16

Instantaneous, but 0.137 seconds

to zero current

IEEE setting

> 51

0.16

0.098

IEEE setting

< 49

0.16

0.102

User setting

> 52

1.00

0.605

User setting

< 48

1.00

0.656

The acceptance ranges are selected using the system display. The options are IEEE and USER. The
default setting is USER.

¾ The IEEE option allows a range of 206 to 250 Vac at 49 to 51 Hz.
¾ The USER option is not a fixed setting. It follows the ac1/grid lower limit and ac1/grid upper limit settings as

shown on the tables beginning on page 47. The default is a range of 208 to 252 Vac at 48 to 52 Hz.

Reconnection delay is 12 seconds after restoration of acceptable conditions. Sell delay is one minute.
These settings are not adjustable.