Specifications, Table 18 24-volt inverter settings (mate) – Outback Power Systems GFX International Series Operators Manual User Manual
Page 50
Specifications
48
900-0112-01-00 Rev B
Table 18
24-Volt Inverter Settings (MATE)
Field Item Default
Minimum
Maximum
search sensitivity (see page 14 for increments)
6 0 50
search pulse length
8 4 20
Search
search pulse spacing
60 AC cycles
4 AC cycles
120 AC cycles
ac transfer control
Grid
Grid or Gen
ac1/grid limit
25 Aac
2.5 Aac
30 Aac
Input
ac2/gen limit
25 Aac
2.5 Aac
30 Aac
low battery cut-out (LBCO)
21 Vdc
18 Vdc
24 Vdc
low battery cut-in (LBCI)
25 Vdc
20 Vdc
28 Vdc
Inverter
adjust output voltage
230 Vac
210 Vac
250 Vac
charger limit
5.5 Aac
0 Aac
6 Aac
absorb voltage
28.8 Vdc
26 Vdc
32 Vdc
absorb time limit
1.0 hours
0.0 hours
24.0 hours
float voltage
27.2 Vdc
24 Vdc
30 Vdc
float time period
1.0 hours
0.0 hours
24.0 hours
refloat voltage
25 Vdc
24 Vdc
26 Vdc
equalization voltage
29.2 Vdc
28 Vdc
34 Vdc
Charger
equalization time period
1.0 hours
0.0 hours
24.0 hours
ac1/grid lower limit
208 Vac
140 Vac
220 Vac
ac1/grid upper limit
252 Vac
250 Vac
280 Vac
ac1/grid input limit
25 Aac
2.5 Aac
30 Aac
Grid
ac1/grid transfer delay
6 AC cycles
0 AC cycles
240 AC cycles
gen input connect delay
0.5 minutes
0.2 minutes
15 minutes
ac2/gen lower limit
208 Vac
140 Vac
220 Vac
ac2/genupper limit
252 Vac
250 Vac
280 Vac
ac2/gen input limit
25 Aac
2.5 Aac
30 Aac
ac2/gen transfer delay
6 AC cycles
0 AC cycles
240 AC cycles
Generator
(Gen)
ac2/gen support
ON
ON or OFF
aux output control
AUTO
ON, OFF, or AUTO
aux output function
Cool Fan
Cool Fan, DivertDC, DivertAC, AC Drop, Vent
Fan, Fault, GenAlert, LoadShed, or Remote
genalert on voltage
22 Vdc
20 Vdc
28 Vdc
genalert on delay
4 minutes
0 minutes
240 minutes
genalert off set point
28 Vdc
24 Vdc
36 Vdc
genalert off delay
9 minutes
0 minutes
240 minutes
load shed off voltage
22 Vdc
20 Vdc
28 Vdc
vent fan on set point
26 Vdc
20 Vdc
32 Vdc
vent fan off period
5 minutes
0 minutes
30 minutes
diversion on voltage
29.2 Vdc
24 Vdc
32 Vdc
Auxiliary
(AUX)
diversion off delay
30 seconds
0 seconds
240 seconds
Stacking
stack phase
Master
Master, OB Slave L1, 3p Classic B, 3p Classic C
master adjust only
0 0 7
Power
Save
slave adjust only
1 1 15
sell re volts
26 Vdc
20 Vdc
30 Vdc
grid tie window
User
IEEE or User
Sell
grid tie authority
GridTie
GridTie or NoSell
vac input adjustment
3
236 220 254
vac output adjustment
3
236 220 254
Calibration
(Cal)
battery vdc adjustment
4
2 0 4
3
These values are in digital counts, not volts. Lower counts stand for higher voltages, and higher counts mean lower voltages. One count equals approximately
1 Vac. The range of adjustment is 15 Vac above nominal and 17 Vac below nominal.
4
These values are in digital counts, not volts. One count equals 0.2 Vdc. The range of adjustment is 0.4 Vdc above or below nominal.