Specifications, Environmental specifications, Server specifications – HP ProLiant SL335s G7 Server User Manual
Page 67
Specifications 67
Specifications
Environmental specifications
Specification
Value
Temperature range*
Operating
10°C to 35°C (50°F to 95°F)
Shipping
-30°C to 50°C (-22°F to 122°F)
Storage
-30°C to 60°C (-22°F to 140°F)
Maximum wet bulb temperature 28°C (82.4°F)
Relative humidity
(noncondensing)**
Operating
10% to 90%
Non-operating
5% to 95%
* All temperature ratings shown are for sea level. An altitude derating of 1°C per 300 m (1.8°F per 1,000 ft) to 3048
m (10,000 ft) is applicable. No direct sunlight allowed.
** Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F). Altitude maximum for
storage corresponds to a pressure minimum of 70 KPa.
Server specifications
Specification
Value
Dimensions
Height
17.68 cm (6.96 in)
Depth
89.71 cm (35.32 in)
Width
44.8 cm (17.63 in)
Weight (maximum)
84 kg (185.2 lb)
Weight (no drives installed)
60 kg (132.3 lb)
Input requirements
Rated input voltage
90–140 VAC
180–264 VAC
Rated input frequency
47–63 Hz
Rated input current
7.31 A at 115 VAC
3.6 A at 230 VAC
Rated input power
855 W at 100 VAC input
840.72 W at 200 VAC input
Btus per hour
N/A
Power supply output
Rated steady-state power
750 W at 100 VAC input
1200 W at 200–240 VAC input
System input requirements information is based on measurements with hardware available at the time of publishing this
document. For updated information, see the HP website