User configuration items – American Power Conversion SMARTUPS 450 User Manual

Page 30

background image

26

Note: Setting these items requires optional software or hardware.

Function

Factory
Default

User Selectable

Choices

Description

Automatic Self-Test

Every 14

days (336

hours)

Every 7 days (168
hours), On Startup
Only, No Self-Test

Sets the interval at which the unit will
execute a self-test.

Unit ID

UPS_IDEN

Up to eight characters
to define the unit.

Use this field to uniquely identify the
unit for network management
purposes.

Date of Last Battery
Replacement

Manufacture

Date

Date of Battery
Replacement

Reset this date on battery replacement.

Minimum Capacity
Before Return from
Shutdown

0 percent

15, 50, or 90 percent

The unit will charge its batteries to the
specified percentage before return
from a shutdown.

Sensitivity

Normal

Reduced, Low

Set lower than normal sensitivity to
avoid lowered battery capacity and
service life in situations where the load
can tolerate minor power disturbances.

Duration of Low
Battery Warning

2 minutes

5, 7, or 10 minutes

Sets the time before shutdown at
which the unit issues a low battery
warning. Set higher than the default
only if the OS needs the time for
graceful shutdown.

Alarm Delay After
Line Fail

5 second

delay

30 second delay, At
Low Battery
Condition, No Alarm

To avoid alarms for minor power
glitches, set the alarm delay.

Shutdown Delay

20 seconds

180, 300, or 600
seconds

Sets the interval between when the
unit receives a shutdown command
and when shutdown occurs.

Synchronized Turn-on
Delay

0 seconds

60, 180, 300 seconds

To avoid branch circuit overload, the
unit will wait the specified time after
the return of utility power before
turn-on.

High Transfer Point

132 Vac

135, 138, 129 Vac

Low Transfer Point

103 Vac

100, 97, 106 Vac

14. User Configuration Items