Specifications – American Power Conversion SMARTUPS 450 User Manual
Page 27

23
English
*Adjustable via optional software.
12. Specifications
450 VA
700 VA
1000 VA
1400 VA
2200 VA
3000 VA
Acceptable input voltage
0 - 160 VAC
Maximum input voltage range*
92-146 VAC
Output voltage*
103-132 VAC
Nominal input frequency
50 or 60 Hz, autosensing
Input Protection
Resettable circuit breaker
Frequency limits (on-line operation)
50 or 60 Hz, ±5%
Transfer time
2 ms typical, 4 ms maximum
Maximum load
450 VA
280 W
700 VA
450 W
1000 VA
670 W
1400 VA
950 W
2200 VA
1600 W
3000 VA
2250 W
On-battery output voltage
115 VAC
On-battery frequency
50 or 60 Hz, ±0.1 Hz; unless synchronized to utility during
brownout.
On-battery waveshape
Low-distortion sine wave
Protection
Overcurrent and short-circuit protected, latching shutdown on
overload
Surge energy rating
(one time, 10/1000 µs waveform)
320 J
480 J
Surge current capability
(one time, 8/20 µs waveform)
6500 A maximum
Surge response time
0 ns (instantaneous) normal mode;
<5 ns common mode
Surge voltage let-through
(percentage of applied ANSI C62.41 Cat. A
±6 kV test waveform)
0.70%
0.30%
Noise Filter
Normal and common mode EMI/RFI suppression,
100 kHz to 10 MHz
Battery type
Spill proof, maintenance free, sealed lead-acid
Typical battery life
3 to 6 years, depending on number of discharge cycles and
ambient temperature
Typical recharge time