24 lonworks gateway – LG PQNFB16A1 User Manual
Page 24
Appendix
24 Lonworks Gateway
1: Air conditioner, ventilation low fan
2: Air condition med fan, ventilation high fan
value
3: Air condition high fan, ventilation very high fan
4: Air condition, ventilation auto fan
5. Air conditioner super low fan
state
0: Product not applied, 1: Product applied
Default Value
3) Fan level command input/output (Air conditioner/ventilation)
Valid Range
SNVT_switch
( Index : 95 )
NV
Filed
Operation
Function
Fan level command input
Input
Using NV
Network input variable : SNVT_switc nviFanSpeedCmd_n
Operation
It controls the fan level of each indoor unit.
Function
Fan level status display
Output
Using NV
Network output variable : SNVT_switch nvoFanSpeed_n
Operation
It monitors the fan level of each product (air conditioner/ventilation)
value
not used (set in 0% usually)
0 = Air conditioner/ventilation product lock OFF
state
1 = Air conditioner/ventilation product lock ON
Default Value
4) Lock input/output (Air conditioner/ventilation)
Valid Range
SNVT_switch
( Index : 95 )
NV
Filed
Operation
Function
Lock setting command input
Input
Using NV
Network input variable : SNVT_switch nviLock_n
Operation
It controls the lock status of each product (air conditioner/ventilation)
Function
Lock status display
Output
Using NV
Network output variable : SNVT_switch nvoLock_n
Operation
It monitors the lock status of each product (air conditioner/ventilation)