BNU-LW remote diagnosis function

Installation Manual 15

ENGLISH

1. Connect the LAN line between the PC

and the LAN port of the BNU-LW.

2. Set the network IP of the used PC to

192.168.1.xxx (except 101).

3. Enter 192.168.1.101 in the Internet

Explorer.

4. The above picture is shown when

connected normally.

• Initial ID: lonwork

• Initial password: lonwork

• Enter the total number of connected

indoor units in the Total Unit block.

BNU-LW remote diagnosis function

Setting method