beautypg.com

Air conditioner control/monitoring point, English – LG PQNFB16A1 User Manual

Page 21

background image

Appendix

Installation Manual 21

ENGLISH

Air conditioner control/monitoring point

1

ON/OFF (setting)

SNVT_switch nviOnOff_nn

input

Stop

Operation

2

ON/OFF (status)

SNVT_switch nvoOnOff_nn

output

Stop

Operation

3

Lock (setting)

SNVT_switch nviLock_nn

input

Cancel

Setting

4

Lock (status)

SNVT_switch nvoLock_nn

output

Cancel

Setting

5

Operation Mode (setting)

SNVT_hvac_modenviHeatCool_nn

input

Auto

Heating

Cooling

Fan

Dry

6

Operation Mode (status)

SNVT_hvac_mode nviHeatCool_nn

output

Auto

Heating

Cooling

Fan

Dry

7

Swing(setting)

SNVT_switch nviSwing_nn

input

Cancel

Setting

8

Swing(status)

SNVT_switch nvoSwing_nn

output

Cancel

Setting

9

Fan speed(setting)

SNVT_switch nviFanSpeedCmd_nn

input

Low

Med

High

Auto

Super Low

10

Fan speed(status)

SNVT_switch nvoFanSpeed_nn

output

Low

Med

High

Auto

Super Low

11

Set Room Temperature

SNVT_temp_p nviSetPointCmd_nn

input

°C

12

Set Room Temperature

SNVT_temp_p nvoSetPoint_nn

output

°C

13

Room Temperature

SNVT_temp_p nvoSpaceTemp_nn

output

°C

14

Error Code

SNVT_hvac_status nvoUnitStatus_nn

output

no errorRefer to the LG Air Conditioner Error Code.

Point

No.

Name

Object

Type

Unit

code 0

code 1

code 2

code 3

code 4

code 5

code 9

code

14

Object Name

(nn: Air conditioner and ventilation

group/indoor unit address)