Ventilation control/monitoring point – LG PQNFB16A1 User Manual
Page 22
Appendix
22 Lonworks Gateway
Ventilation control/monitoring point
1
ON/OFF (setting)
SNVT_switch nviOnOff_nn
input
Stop
Operation
2
ON/OFF (status)
SNVT_switch nvoOnOff_nn
output
Stop
Operation
3
Lock (setting)
SNVT_switch nviLock_nn
input
Cancel
Setting
4
Lock (status)
SNVT_switch nvoLock_nn
output
Cancel
Setting
5
Operation Mode (setting)
SNVT_hvac_modenviHeatCool_nn
input
Auto
Heat exchange
Normal
6
Operation Mode (status)
SNVT_hvac_mode nviHeatCool_nn
output
Auto
Heat exchange
Normal
7
Fan speed(setting)
SNVT_switch nviFanSpeedCmd_nn
input
Low
High
Very high
8
Fan speed(status)
SNVT_switch nvoFanSpeed_nn
output
Low
High
Very high
9
Error Code
SNVT_hvac_status nvoUnitStatus_nn
output
Refer to the LG Air Conditioner Error Code.
10
User Mode(setting)
SNVT_count nviUser_nn
output
Quick
Power save
heat
11
User Mode(status)
SNVT_count nvoUser_nn
output
Quick
Power save
heat
Point
No.
Name
Object
Type
Unit
code 0
code 1
code 2
code 3
code 5
code 9
Object Name
(nn: Air conditioner and ventilation
group/indoor unit address)