Operation: Operation Procedures

12

Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001

Press Initiate Transfer.

Verify that the status in the upper right corner of the
screen has changed to Static bypass.

How to transfer from static bypass to normal operation

Press the Operation button on the UPS Summary
screen.

Press the Static Bypass -> Online button. Press
inside the password field and type in the user
password using the keyboard on the screen.
Complete with Enter.

Press Initiate Transfer.

Verify that the status in the upper right corner of the
screen has changed to Normal.