Installation

LTPH-UM-1237-04

12

July 21, 2004

HRM-238 List 1

Verify Cabling

Verify the following:

1

Verify a minimum of -42 Vdc and a maximum of -56 Vdc between the following:

a

-48 Vdc battery screw Terminal 1 and the battery common Terminal 3 (BATTERY RETURN)

b

-48 Vdc battery screw Terminal 2 (when used) and the battery common Terminal 3 (BATTERY
RETURN)

2

Visually verify that all connections are securely terminated.

Secure Cabling

Tie the cable connectors to the back of the HRM-238 shelf using the tie wraps and mounting screws.

I

NSTALLING

THE

M

ANAGEMENT

U

NIT

(

S

)

1

Install the management unit(s) into the HRM-238 shelf per procedures in the appropriate HMU-319 user
manual.

2

Loosen the security bracket screw, push down the security bracket, and re-tighten the screw (

Figure 6 on

page 5

).