LTPH-UM-1237-04

Installation

HRM-238 List 1

July 21, 2004

5

I

NSTALLATION

I

NSPECTING

Y

OUR

S

HIPMENT

Upon receipt of the equipment:

Unpack each container and inspect the contents for signs of damage. If the equipment has been damaged in
transit, immediately report the extent of damage to the transportation company and to ADC
Telecommunications, Inc. Order replacement equipment, if necessary.

Check the packing list to ensure complete and accurate shipment of each listed item. If the shipment is short
or irregular, contact ADC as described in

“Appendix B - Product Support” on page 14

. If you must store the

equipment for a prolonged period, store the equipment in its original container.

I

NSTALLING

THE

HRM-238 S

HELF

Install the HRM-238 in a CO equipment bay rack. If the CO rack is 19 inches wide, attach the short side of the
mounting bracket to the HRM-238 shelf and use the long side of the mounting bracket to attach to the CO rack.
If the CO rack is 23 inches wide, reverse the mounting bracket. Attach the long side of the mounting bracket to
the HRM-238 shelf and use the short side of the mounting bracket to attach to the CO rack (

Figure 6

).

1

Position the HRM-238 shelf in the CO rack. (See

“Operational Capabilities” on page 2

, and

Figure 2 on

page 2

,

Figure 3 on page 3

, or

Figure 4 on page 3

for recommended placement.)

2

Align the HRM-238 shelf mounting brackets with the vertical mounting holes on the CO rack (

Figure 6

).

3

Install the mounting hardware and secure.

Figure 6.

Shelf with Brackets Positioned for 19-inch Rack

I

NSTALLING

F

RAME

G

ROUND

AND

B

ATTERY

P

OWER

Perform the following steps to install the -48 Vdc battery to the HRM-238 shelf and to connect battery common
ground (LGND) and frame ground (FGND). The HRM-238 shelf terminal block TB1 has two connection points
for supplying redundant battery capability. Connect a -48 Vdc battery source to Terminal 1 (-48V_A) to supply
voltage to the HRM-238 shelf (

Table 2 on page 6

). Connect another -48 Vdc battery source to Terminal 2

(-48V_B) to supply redundant voltage to the HRM-238 shelf. See

Table 2 on page 6

for TB1 terminal block

information.

A

B

Mounting bracket

H0546-B

Mounting bracket

Security bracket