4. 0 UNLOAD 1 Selection

a) PROBABLE CAUSES;

1a) Rear Panel Disconnect Plug.

2a) Defective Switch.

3a) Wiring Back to Main Electrical Enclosure.

b) POSSIBLE SOLUTIONS;

1b) If the O UNLOAD 1 Switch does not respond when selected:

• Verify that the rear panel controls disconnect plug is indeed connected. This disconnect plug

allows for the removal of the rear control panel for drying servicing.

2b) Defective O UNLOAD 1 Selector Switch

• Shut power off at the main breaker and remove the rear panel and check switches using an OHM

meter; replace if defective.

3b) Wiring Back to the Main Electrical Enclosure

• With the control voltage “ON” Front Panel Green Button

• Select “1” on the “O UNLOAD” switch located on the rear control panel. Does the PLC

(Programmable Logic Controller) IN PIN 19 = UNLOAD, REAR PANEL light?

• If yes, refer to paragraph 3a on page 76.

• If no, refer to paragraph 4b on page 76.

4b) The L.E.D. (light emitting diode) “ON” on the PLC (Programmable Logic Controller) indicates are

also illuminating when the O UNLOAD 1 selector switch is on “1”.

PLC OUT PIN 7 = UNLOAD DOOR (OPEN)

PLC OUT PIN 10 = FRONT UP

• If output indicators are functional, however the UNLOAD DOORS or FRONT UP commands

are not executed correctly:

• Check wiring on the MAIN ENCLOSURE PANEL (refer to the ML-460 MAIN PANEL

WIRING DIAGRAM)

• Check wiring associated with the Solenoid Junction Box

• Refer to troubleshooting procedures associated with the Solenoid Junction Box