2. Electrical Service Specifications

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is

affixed to the right side of the main electrical enclosure. In the case of 208 VAC or
240 VAC, the supply voltage must match the electric service specifications of
the data label exactly.

WARNING: 208 VAC and 240 VAC ARE NOT THE SAME. Any damage done to the dryer

components due to improper voltage will automatically VOID THE WARRANTY.

IMPORTANT: For proper sprinkler and dryer operation, sprinkler must be powered by a “separate

or dedicated” single-phase (1ø) multi-wire branch circuit at dryer’s nameplate voltage.

NOTE: For 4-wire service, cap the neutral.

NOTE: Contact the factory for electrical information not listed.

NOTE: ADC reserves the right to make changes in specifications at any time, without notice or

obligation.

MLG-460

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

exact voltage .
NOTES
:

A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.

B.

Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to
appliance
amp draw rating and type of breaker used.

C. Circuit breakers for 3Ø dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

MINIMUM

WIRE SIZE*

FUSING

CIRCUIT

BREAKER

60 Hz

50 Hz

Dual Element

Time Delay

208

3/4

107

---

1/0

150

150

240

3

104

109

1/0

150

150

380

3/4

---

60

4

100

90

416

3/4

---

57

4

90

90

460

3/4

52

---

4

80

90

DEDICATED SPRINKLER SERVICE

Dryer

Nameplate

---

2

16

3.5

5

* AWG Stranded Wire Type...for individual lengths less than 100 feet (31 m).