Parameters, Further documentation and software (www.nord.com) – NORD Drivesystems TI 278910140 User Manual
Page 4
Control box – SK POT1-2
4
TI 278910140 - 3313
Parameters
For the correct function of the control box, the following frequency inverter parameters must be
modified (for details, please refer to the frequency inverter manual).
Parameter [-Array]
Meaning
Setting / Remarks
SK 180E,
SK 190E,
SK 2x0E,
SK 54xE
SK 2x5E with
SK xU4-IOE
SK 500E …
SK 535E
P400 [-01]
P400 [-03]
P400
Analog input function
"01" = Setpoint frequency
P420 [-01]
P480 [-05]
P420
Digital input (1)
"01" = Enable right
P420 [-02]
P480 [-06]
P421
Digital input (2)
"02" = Enable left
Optional (if required)
P428
P428
P428
Automatic start with
"Mains On"
"01" = On (automatic start enabled)
Pos : 8 /T ec hnis che Inf or mationen/ Bedi enboxen [SK POT 1-.. .]/ Weit erführende Dokumentationen und Soft ware [ SK PO T1-. ..] @ 3\ mod_1368009833611_388. doc x @ 64839 @ 5 @ 1
Further Documentation and Software
Software
Name
Software
Meaning
NORD CON
Parameterisation and diagnostic software
Document
Name
Document
Meaning
BU 0000
Description of the NORD CON software
BU 0200
SK 2xxE frequency inverter manual
BU 0040
ParameterBox manual
BU 0500
SK 500E – SK 535E frequency inverter manual
BU 0190
Frequency inverter manual SK 180E, SK 190E
BU 0505
SK 540E – SK 545E frequency inverter manual
=== Ende der List e f ür T ext mar ke I nhalt ===