NORD Drivesystems TI 275281118 User Manual
Technical information / datasheet, Sk tu4, Attention
![background image](/manuals/372830/1/background.png)
Technical Information / Datasheet
POWERLINK Bus module
SK TU4-POL
1.1
LED - displays, technical datas, Error 10.9
4913
Rck
TI 275281118
GB
version
reason for change(s)
issue
name
document
speech
Pos : 2 /T ec hnis che Inf or mationen/ SK xU x - Bus - Er wei ter ung en/ Powerlink/SK TU 4-PO L / 275281118 / Basisinf or mationen [SK TU 4-POL] @ 3\ mod_1377869062268_388.doc x @ 92132 @ 555 @ 1
SK TU4
-
POL
Part number: 275 281 118
POWERLINK - External bus interface
ATTENTION
Validity of the documents
This document is only valid in combination with the operating instructions for the relevant frequency inverter.
All of the information that is relevant for a safe start-up of this module and the frequency inverter is only available
under these conditions.
Scope of delivery
1 x
Module
SK TU4-POL
4 x
Hexagon socket
M4 x 40 mm
Accessories required:
1 x
Bus connection unit
SK TI4-TU-BUS
TI 275280000 Part No. 275 280 000)
Field of use
External technology unit for connecting a decentralised frequency inverter (SK 180E … SK 2xxE) to a
POWERLINK field bus. The module can be fitted to or in the immediate vicinity of the frequency
inverter. It is connected to the inverter via the system bus, and can communicate directly with up to 4
frequency inverters. 8 digital inputs and 2 digital outputs are available.
Technical data
Module
Temperature range
-25 °C … 50 °C
Vibration resistance
3M7
Temperature class
Class 3k3
Firmware version
V1.2 R0
Protection class
IP55
Hardware version
AA
Supply voltage
24 V ± 20
%, ≈ 100 mA
Reverse polarity protected
Dimensions [mm]*
H x W x D: 95 x 136 x 99
* module fitted to BUS
-
connection unit
Depth: 108mm with covers on M12
-
connection
Digital input - working area
Low: 0 V … 5 V, High: 15 V … 30 V
Digital input - specific data
R
i
= 8
kΩ, input capacity: 10nF, reaction time 1 ms, inputs
according to EN 61131-2 type 1
Digital output - 24 VDC power supply
≤ 400 mA (input)
Digital output - working area
Low = 0 V, High = 24 V; max. 200 mA