NORD Drivesystems TI 275271018 User Manual
Page 5
POWERLINK Bus module – SK CU4-POL
TI 275271018 - 4913
5
POWERLINK-specific LEDs
BS
(Module status)
Meaning
OFF
No communication
Flashing green 1x
Pre Operational 1: Parameter communication active, no process data
Flashing green 2x
Pre Operational 2: as for Pre Operational 1
Flashing green 3x
Ready To Operate: Parameter communication active, restricted process data communication
Green ON
Operational: Parameter communication active, process data communication active
Flashing green (10 Hz)
Basic Ethernet: Parameter communication active via UDP, no process data
Flashing green (2.5 Hz)
Stopped: No communication
BE
(Network Error)
Meaning
OFF
No POWERLINK error
Red ON
General POWERLINK error
L/A
(Green LED)
Meaning
OFF
•
Module not ready, no control voltage.
•
No bus connection (check cable connection)
Flashing green
•
Technology box connected and active
Green ON
Technology unit ready, but
•
no bus activity available
Pos : 21 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/ LED Anz eigen- N ORD s pezifisc he LED [EI P / PO L / ECT / PNT Allgemei n] @ 3\ mod_1363773424248_388. doc x @ 61815 @ @ 1
NORD-specific LEDs
DS
(Device status)
DE
(Device error)
Meaning
Long flash
= 0.5 s on / 1 s off
Short flash
= 0.25 s on / 1 s off
OFF
OFF
Module not ready, no control voltage.
ON
OFF
Module ready, no error, at least one frequency inverter is communicating via the system bus
ON
Short flashing
Module ready, but
•
One or more of the connected frequency inverters has fault status
Long flashing
OFF
Module ready and at least one other participant is connected to the system bus, but
•
no frequency inverter connected to system bus (connection may be interrupted)
•
one or more system bus clients has address error
•
Software incompatible (module software and FI software do not match - update required)
Long flashing
Short flashing
Flash interval
1 x - 1s pause
System bus is in status "Bus Warning"
•
Communication on system bus disrupted
•
No other clients available on system bus
•
Module not inserted correctly or no connection to the system bus
•
Frequency inverter has no supply voltage
Long flashing
Short flashing
Flash interval
2 x - 1s pause
System bus is in status "Bus Off"
•
the system bus 24V power supply was interrupted during operation
Long flashing
Short flashing
Flash interval
3 x - 1s pause
System bus is in status "Bus Off"
•
No system bus 24V power supply
Long flashing
Short flashing
Flash interval
4 x - 1s pause
Module error
•
see parameter P170
OFF
Short flashing
Flash interval
1…7 - 1s pause
System error, internal program sequence interrupted
•
EMC interference (observe wiring guidelines!)
•
Module defective