NORD Drivesystems TI 275271018 User Manual

Page 5

background image

POWERLINK Bus module – SK CU4-POL

TI 275271018 - 4913

5

POWERLINK-specific LEDs

BS

(Module status)

Meaning

OFF

No communication

Flashing green 1x

Pre Operational 1: Parameter communication active, no process data

Flashing green 2x

Pre Operational 2: as for Pre Operational 1

Flashing green 3x

Ready To Operate: Parameter communication active, restricted process data communication

Green ON

Operational: Parameter communication active, process data communication active

Flashing green (10 Hz)

Basic Ethernet: Parameter communication active via UDP, no process data

Flashing green (2.5 Hz)

Stopped: No communication

BE

(Network Error)

Meaning

OFF

No POWERLINK error

Red ON

General POWERLINK error

L/A

(Green LED)

Meaning

OFF

Module not ready, no control voltage.

No bus connection (check cable connection)

Flashing green

Technology box connected and active

Green ON

Technology unit ready, but

no bus activity available

Pos : 21 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/ LED Anz eigen- N ORD s pezifisc he LED [EI P / PO L / ECT / PNT Allgemei n] @ 3\ mod_1363773424248_388. doc x @ 61815 @ @ 1

NORD-specific LEDs

DS

(Device status)

DE

(Device error)

Meaning
Long flash

= 0.5 s on / 1 s off

Short flash

= 0.25 s on / 1 s off

OFF

OFF

Module not ready, no control voltage.

ON

OFF

Module ready, no error, at least one frequency inverter is communicating via the system bus

ON

Short flashing

Module ready, but

One or more of the connected frequency inverters has fault status

Long flashing

OFF

Module ready and at least one other participant is connected to the system bus, but

no frequency inverter connected to system bus (connection may be interrupted)

one or more system bus clients has address error

Software incompatible (module software and FI software do not match - update required)

Long flashing

Short flashing

Flash interval

1 x - 1s pause

System bus is in status "Bus Warning"

Communication on system bus disrupted

No other clients available on system bus

Module not inserted correctly or no connection to the system bus

Frequency inverter has no supply voltage

Long flashing

Short flashing

Flash interval

2 x - 1s pause

System bus is in status "Bus Off"

the system bus 24V power supply was interrupted during operation

Long flashing

Short flashing

Flash interval

3 x - 1s pause

System bus is in status "Bus Off"

No system bus 24V power supply

Long flashing

Short flashing

Flash interval

4 x - 1s pause

Module error

see parameter P170

OFF

Short flashing

Flash interval

1…7 - 1s pause

System error, internal program sequence interrupted

EMC interference (observe wiring guidelines!)

Module defective