Configuration, Led displays, Ethercat bus module – sk cu4-ect – NORD Drivesystems TI 275271017 User Manual
Page 4: Ethercat-specific leds

EtherCAT Bus module – SK CU4-ECT
4
TI 275271017 - 4913
Configuration
In general, no settings need to be made on the device. However, via the "Hot Connection Group"
functionality, the module can be configured with a fixed address, the so-called "Second Address". This
is carried out via the DIP switches of the module. The DIP switch settings are read after a "Power On"
of the module.
DIP switch
Meaning
12
11
10
9
8
7
6
5
4
3
2
1
Address
0
0
0
0
0
0
0
0
0
0
0
X
0
0
0
0
0
0
0
0
0
0
0
1
X
1
0
0
0
0
0
0
0
0
0
1
0
X
2
-
-
-
-
-
-
-
-
-
-
-
X
-
1
1
1
1
1
1
1
1
1
1
1
X
2047
0
System bus
terminating resistor
not set
1
System bus
terminating resistor
set
Pos : 18 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Et herC at/ LED Anz eigen [ SK CU4- ECT] @ 3\ mod_1371817321544_388. doc x @ 79531 @ 5 @ 1
LED displays
The operating statuses of the module are visualised using LED indicators.
No.
Name
Colour
Meaning
1
RUN
green
Ethernet State
ERR
red
Ethernet Error
2
DS
green
Device status
DE
red
Device error
3
L/A IN
green
Link/Activity In
L/A OUT
green
Link/Activity OUT
Pos : 20 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Et herC at/ LED Anz eigen- EtherCAT spezifis che LED [ ECT Allgemei n] @ 3\ mod_1371732026091_388. doc x @ 79187 @ @ 1
EtherCAT-specific LEDs
RUN
State
Meaning
OFF
Init
•
No communication of process data and parameters
Flashing
Pre-Operational
•
Parameter communication active
•
No process data communication
Single Flash
Save
Operational
•
Parameter communication active
•
Limited process data communication
•
No restriction of actual values
•
Setpoints not evaluated
ON
Operational
•
Parameter communication active
•
Unrestricted process data communication
ERR
State
Meaning
OFF
No Error
•
EtherCAT functioning normally on the Bus Module
Flashing
Invalid
Configuration
•
General EtherCAT configuration error
This can be generated by an incorrect XML file.
Single Flash
Unsolicited
State Change
•
The module has changed the EtherCAT state without authorisation
Double Flash
Application
Watchdog
Timeout
•
EtherCAT or FI timeout (P513 in FI)
1
…
12
ON
OF
F