Installation and parameterisation

BU 0930 GB-0612

Subject to technical amendments

5

According to the setting of the key switch, the contacts are
closed in the following manner:

Key switch

position

Contact 1-3 / 1-4

Contact 2-3 / 2-4

I

closed

open

O

open

open

II

open

closed

3 Parameterisation

To ensure the correct function of the SK OPR1-AUM control box, the following parameters must be
changed in the frequency inverter.

The most important of these are listed below. For further information, please refer to the manual for the
relevant frequency inverter.

NOTE

The direction of rotation stated in the following parameterisation recommendations
"Recommended Settings" must be made according to the specified direction of rotation of
the system or gear unit and may if necessary also have the value {02} "Enable Left"

SK 200E

Digital
input

Parameter

Factory setting

Recommended
setting

Comments

DIN 1

P420 [-01]

{01} "Enable right"

{01} "Enable right"

DIN 2

P420 [-02]

{02} "Enable left"

{01} "Enable right"

with (P428) "Automatic start": {ON}

DIN 3

P420 [-03]

{04} "Fixed frequency 1"

{04} "Fixed frequency 1"

Value FF1: E.g.: {6.0} in (P465[-01])

DIN 4

P420 [-04]

{05} "Fixed frequency 2"

{05} "Fixed frequency 2"

Value FF2: E.g.: {55.5} in (P465[-02])

SK CU1-STD / SK CU1-MLT (for SK 750E)

Digital
input

Parameter

Factory setting

Recommended
setting

Comments

DIN 1

P420

{01} "Enable right"

{01} "Enable right"

DIN 2

P421

{02} "Enable left"

{01} "Enable right"

with (P428) "Automatic start": {ON}

DIN 3

P422

{08} "P. set Bit 0"

{05} "Fixed frequency 2"

Value FF2: E.g.: {6.0} in (P430)

DIN 4

P423

{04} "Fixed frequency 1"

{04} "Fixed frequency 1"

Value FF1: E.g.: {55.5} in (P429)

DIN 5

P424

{00} "No function"

{00} "No function"

only SK CU1-MLT

DIN 6

P425

{00} "No function"

{00} "No function"

only SK CU1-MLT

Illustration of the

function of the

SK OPR1-AUM

e.g. with an

SK CU1-STD / MLT

interface.