NORDAC SK 500E - ERS Information

Control connection details

BU0560_ERS_GB-0512

Subject to technical amendments

3


Wires with a cross-section of 0.2mm² to 1.5mm² (without wire end sleeve) can be connected to the spring
terminals. The type code -ERS is the abbreviation for this special version.

Terminal

Function
[factory setting]

Data

Description / wiring suggestion

Parameter


Terminal block X11

(1x RJ12), RS485/RS232

1 RS485

A

Data cable RS485

Baud rate
9600…38400Baud
Terminal resistance
R=120

 DIP 1 (see

below)

RS

4

8

5

_

A

RS

4

8

5

_

B

GN

D

TX

D

RX

D

+5

V

RJ12: Pin No. 1 … 6

P502...P513

2 RS485

B

3 GND

Reference potential for
Bus signals

0V digital

4,232 TXD

Data cable RS232

Baud rate
9600…38400Baud

5,232 RXD
6 +5V

internal 5V supply
voltage

5V

 20%

optional

Adapter cable
RJ12 to SUB-D9
for direct connection
to a PC with NORD
CON

Length 3m
Assignment RS 232
(RxD, TxD, GND)

TxD

RxT

GND

+ 5V

n.c.

n.c.

Part. No. 278910240


DIP switches1/2

(top view of SK 5xxE)

Plug designation

X11

X9

R

S

485

_

A

R

S

485

_

B

GN

D

TX

D

RX

D

+5

V

1 2

ON

RS232/485

DIP

CAN/CANopen

DIP switch 1

Terminal resistor for RS485 interface
(RJ12); ON = switched in

DIP switch 2

Terminal resistor for CAN/CANopen
interface (RJ12); ON = switched in


Terminal block X9, CAN/CANopen

(only SK 500E-…-ERS)

75 CAN_H

CAN/CANopen signal

Baud rate …500kBaud
RJ45 sockets are connected
in parallel internally.
Termination resistor R=120

DIP 2 (see below)

NOTE:

To operate

CANbus/CANopen the
interface must be externally
supplied with 24V (capacity
at least 30mA).









1x spring terminal bar

P502...P515

76 CAN_L
90 CAN_SHD Cable

shield

46 CAN_GND CAN

GND

45 CAN_24V External 24 VDC

power supply

75 CAN_H

CAN/CANopen signal

76 CAN_L