Electric Actuators Performance Rating

MAINTENANCE/REPAIR
Upon final installation of the Series WE, only routine maintenance is required. The
Series WE is not field serviceable and should be returned if repair is needed. Field
repair should not be attempted and may void warranty.

WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact
customer service to receive a Return Goods Authorization number before shipping
the product back for repair. Be sure to include a brief description of the problem
plus any additional application notes

TI03 and MI03
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
5 s
25%
75%
0.75 A
300 in-lb

220 VAC
5 s
25%
75%
0.38 A
300 in-lb

24 VAC
5 s
25%
75%
3.2 A
300 in-lb

24 VDC
5 s
25%
75%
3.2 A
300 in-lb

TI04 and MI04
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
10 s
25%
75%
0.75 A
400 in-lb

220 VAC
10 s
25%
75%
0.38 A
400 in-lb

24 VAC
10 s
25%
75%
3.2 A
400 in-lb

24 VDC
10 s
25%
75%
3.2 A
400 in-lb

TI05 and MI05
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
15 s
25%
75%
0.75 A
625 in-lb

220 VAC
15 s
25%
75%
0.38 A
625 in-lb

24 VAC
15 s
25%
75%
3.2 A
625 in-lb

24 VDC
15 s
25%
75%
3.2 A
625 in-lb

TI06 and MI06
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
15 s
25%
75%
1.1 A
1000 in-lb

220 VAC
15 s
25%
75%
0.38 A
1000 in-lb

24 VAC
15 s
25%
75%
3.2 A
1000 in-lb

24 VDC
15 s
25%
75%
3.2 A
1000 in-lb

TI07 and MI07
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
30 s
25%
75%
1.1 A
1500 in-lb

220 VAC
30 s
25%
75%
0.38 A
1500 in-lb

24 VAC
30 s
25%
75%
3.2 A
1500 in-lb

24 VDC
30 s
25%
75%
3.2 A
1500 in-lb

TI08 and MI08
Voltage
Cycle Time
Duty Cycle (Two Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
12 s
100%
100%
2.6 A
2000 in-lb

220 VAC
12 s
100%
100%
2.4 A
2000 in-lb

24 VAC
12 s
100%
100%
20 A
2000 in-lb

24 VDC
12 s
100%
100%
20 A
2000 in-lb

TI09 and MI09
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
14 s
100%
100%
2.99 A
3840 in-lb

220 VAC
14 s
100%
100%
2.4 A
3840 in-lb

24 VAC
14 s
100%
100%
20 A
3840 in-lb

24 VDC
14 s
100%
100%
20 A
3840 in-lb

TI10 and MI10
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
68 s
100%
100%
2.99 A
5000 in-lb

220 VAC
68 s
100%
100%
2.4 A
5000 in-lb

24 VAC
68 s
100%
100%
20 A
5000 in-lb

24 VDC
68 s
100%
100%
20 A
5000 in-lb

TI01 and MI01
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
2.5 s
25%
75%
0.55 A
100 in-lb

220 VAC
2.5 s
25%
75%
0.38 A
100 in-lb

24 VDC
2.5 s
25%
75%
2.44 A
100 in-lb

TD01
Voltage
Cycle Time
Duty Cycle (Two-Position)
AMP Draw
Torque

110 VAC
4 s
85%
0.24 A
177 in-lb

220 VAC
4 s
85%
0.16 A
177 in-lb

24 VDC
4 s
85%
1.28 A
177 in-lb

TD02 and MD02
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
20 s
85%
85%
0.24 A
442 in-lb

220 VAC
20 s
85%
85%
0.16 A
442 in-lb

24 VDC
20 s
85%

1.28 A
442 in-lb

TD03 and MD03
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
30 s
85%
85%
0.57 A
885 in-lb

220 VAC
30 s
85%
85%
0.35 A
885 in-lb

24 VDC
30 s
85%

2.03 A
885 in-lb

TD04 and MD04
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
30 s
85%
85%
0.65 A
1770 in-lb

220 VAC
30 s
85%
85%
0.37 A
1770 in-lb

24 VDC
30 s
85%

3.57 A
1770 in-lb

TD05 and MD05
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
30 s
85%
85%
1.12 A
3540 in-lb

220 VAC
30 s
85%
85%
0.57 A
3540 in-lb

24 VDC
30 s
85%

5.13 A
3540 in-lb

TD06 and MD06
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
45 s
85%
85%
1.18 A
5210 in-lb

220 VAC
45 s
85%
85%
0.60 A
5210 in-lb

24 VDC
45 s
85%

6.04 A
5210 in-lb

MD01
Voltage
Cycle Time
MD01 Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
10 s
85%
0.24 A
265 in-lb

220 VAC
10 s
85%
0.16 A
265 in-lb

24 VAC
10 s
85%
1.28 A
265 in-lb

TI02 and MI02
Voltage
Cycle Time
TI01 Duty Cycle (Two-Position)
MI01 Duty Cycle (Modulating)
AMP Draw
Torque

110 VAC
5 s
25%
75%
0.75 A
200 in-lb

220 VAC
5 s
25%
75%
0.38 A
200 in-lb

24 VAC
5 s
25%
75%
3.2 A
200 in-lb

24 VDC
5 s
25%
75%
3.2 A
200 in-lb

(MD Not Available in 24 VDC)

(MD Not Available in 24 VDC)

(MD Not Available in 24 VDC)

(MD Not Available in 24 VDC)

(MD Not Available in 24 VDC)

24 VAC
4 s
85%
0.28 A
177 in-lb

24 VAC
20 s
85%
85%
1.28 A
442 in-lb

24 VAC
30 s
85%
85%
2.03 A
885 in-lb

24 VAC
30 s
85%
85%
3.57 A
1770 in-lb

24 VAC
30 s
85%
85%
5.13 A
3540 in-lb

24 VAC
45 s
85%
85%
6.04 A
5210 in-lb

24 VAC
2.5 s
25%
75%
2.44 A
100 in-lb