- 7 -

No change in Media
Level Indication

Incorrect Fluid Level
Indication

Incorrect Color
Indicating Fluid Level

No Float

Float sticking, due to contamina-
tion in the fluid level

Float attracted, due to external
ferrous materials within close
proximity.

The float is damaged

Port is blocked

Float attracted, due to contami-
nation in the media

Float sticking, due to external
ferrous materials within close
proximity

The float is damaged

The float is upside down

Flag assembly is upside-down.
(The wrong color is indicating the
liquid level)

Install float

Clean the float and weldment

Remove the ferrous materials
from close proximity

Replace the float

Remove blockage

Clean the float and weldment

Remove the ferrous materials
from close proximity

Replace the float

Invert the float

Rotate the flag assembly 180
degrees (with the end marked
“TOP” uppermost)

Solution

Condition

Possible Cause

Troubleshooting

Note: Increased viscosity increases the response time of the ViewRite indicator

Warnings/Cautions

1. The ViewRite Magnetic Level Indicator must be maintained and installed in strict accordance with

this Instruction Bulletin. Failure to observe this warning could result in serious injuries or damages.

2. The liquids to be monitored must be compatible with the materials of construction. Specifications

of these materials will be provided upon request.