Dwyer CDTR User Manual

Page 2

background image

MOUNTING
1. Cut hole into duct large enough to insert probe.
2. Attach housing ears to duct using the two self-tapping screws provided.
3. Knock out an opening in the housing and attach an electrical fitting to route

electrical wiring. PG11 & PG16 knockouts are molded into the housing.

WIRING

Use maximum 18 AWG wire for wiring to terminals. Refer to Figure 5 for wiring
information.

Selection of Current and Voltage Outputs
Prior to wiring, verify that the current/voltage configuration switches (positions 1 and
2) are set to the desired output type. Refer to Figure 1 to locate the configuration
switches. See Figure 2 for diagram of the current/voltage selection switches. For
voltage output selection, the output can be 0 to 10 VDC, 0 to 5 VDC, 2 to 10 VDC or
1 to 5 VDC. See Figure 3 for the type of voltage output selection switches (positions
3 & 4).

Current / Voltage Outputs
The transmitter may be wired for current or voltage output for both carbon dioxide and
temperature. The transmitter can be powered with either 16 to 35 VDC or 19 to 28
VAC. Wire the transmitter according to Figure 4.

Thermistor and RTD Outputs
Thermistor and RTD passive outputs are located on terminals 7 and 8 and do not
require any power. Passive temperature outputs are not polarity sensitive.

Remote Display
Remote display Model A-449 can be used to display the relative humidity,
temperature, and carbon dioxide. The mini USB plug of the remote display plugs into
the receptor on the side of the housing. After a short warm up time, the display will
begin to show the current temperature and carbon dioxide measurements unless
configured by the user to show only temperature or only carbon dioxide.

ACCESSING MENU pARAMETERS

Step 1: To enter the menu structure, press and simultaneously for

5 seconds (display will show RON parameter).

Step 2: Press or to cycle between menu items.

Step 3: Press to edit the value for the displayed menu item (SET will appear

on display).

Step 4: Press or to adjust the value of the menu item.

Step 5: Press to save the changes (SET will disappear).

Step 6: Repeat Steps 2 through 5 for each of the parameters.

Step 7: To exit the menu at any time, press and hold and

simultaneously for 5 seconds or wait 10 seconds without pushing any buttons.

CO2 CONCENTRATION

OUTPUT SELECTION

TEMPERATURE/

RH OUTPUT SELECTION

VOLTAGE

CURRENT

VOLTAGE

CURRENT

0-10 V

0-20 mA

2-10 V

4-20 mA

0-5 V

0-10 mA

1-5 V

2-10 mA

PASSIVE
TEMPERATURE
SENSOR

RELAY
CONTACT

POWER

SUPPLY

TEMP OR RH

RECEIVER

CO2

RECEIVER

figure 2: Current/Voltage Output

Selection Jumper (pJ1 And pJ2)

figure 3: Output Range Selection Jumper

figure 4: Active Output Wiring Diagram

figure 1: Diagram Of Circuit Board

DOWN PUSH

BUTTON

CONFIGUATION

SWITCHES

TERMINAL

BLOCK

REMOTE DISPLAY

CONNECTOR

UP PUSH BUTTON

ENTER PUSH BUTTON

Optional relay can be used as either a dry contact or low voltage
switched circuit up to 2 A at 30 VDC.

NOTICE