The following menu items apply only to the alarm.

AL

Alarms: Select OFF, Lo, Hi, or HiLo.
OFF

Alarms are turned OFF. No Alarm menu items appear
in the Secondary and Secure menus.

Lo

Low Alarm Only. ALLo appears in the Secondary
Menu.

Hi

High Alarm Only. ALHi appears in the Secondary
Menu.

HiLo

High and Low Alarms. Both share the same Alarm
Relay output.

ALt

Alarm Type: Select AbS or dE
AbS

Absolute Alarm that may be set anywhere within the
values of SPL and SPH and is independent of SP.

dE

Deviation Alarm that may be set as an offset from SP.
As SP is changed the Alarm Point will track with SP.

ALrE

Alarm Reset: Select OnOF or Hold.
OnOF

Automatic Reset.

Hold

Manual Reset. Reset (acknowledge) by simultaneously
pressing the INDEX & DOWN ARROW keys for 5 sec.

ALPi

Alarm Power Interrupt: Select On or OFF.
On

Alarm Power Interrupt is ON.

OFF

Alarm Power Interrupt is OFF.

ALiH

Alarm Inhibit: Select On or OFF.
On

Alarm Inhibit is ON. Alarm action is suspended until
the process value first enters a non-alarm condition.

OFF

Alarm Inhibit is OFF.

ALSt

Alarm Output State: Select CLOS or OPEn.
CLOS

Closes Contacts at Alarm Set Point.

OPEn

Opens Contacts at Alarm Set Point.

ALLP

Alarm Lamp: Select O on or OoFF.
O on

Alarm Lamp is ON when alarm contact is closed.

OoFF

Alarm Lamp is OFF when alarm contact is closed.