Series 616KD Differential Pressure Transmitter

Bulletin P-616KD

Specifications – Installation and Operating Instructions

OPTIONAL

TERMINAL

COVER

5/16

[7.94]

5/8

[15.88]

Ø5/32
[3.97]

MOUNTING

HOLE

2 PLACES

3-21/64

[84.53]

2-13/32

[61.12]

1/2

[12.70]

1/2

[12.70]

1-1/2

[38.10]

2-1/4 [57.15]

2-13/32 [61.12]

7/8

[22.23]

1-1/32

[26.19]

SPECIFICATIONS
Service:
Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Accuracy: ±2.0% FS.
Stability: ±1% FS/yr.
Temperature Limits: 32 to 122°F (0 to 50°C).
Pressure Limits: 2 psi (13.8 kPa).
Thermal Effect on Span: ±0.11% FS/°F (±0.19% FS/°C) typ.
Thermal Effect on Zero: 616KD-X0: 0.6%/°F (1%/°C); 616KD-X1:
0.3%/°F (0.5%/°C); 616KD-X2: 0.2%/°F (0.33%/°C); 616KD-X3:
0.12%/°F (0.2%/°C); 616KD-X4: 0.06%/°F (0.1%/°C) FS max.
Power Requirements: 16 to 36 VDC (2 or 3 wire); 20 to 28 VAC (3
wire).
Output Signal: 4 to 20 mA or unit with field selectable 0 to 10 & 0 to 5
volt.
Zero and Span Adjustments: Push button.
Loop Resistance: DC: 1000 Ω max.; AC: 1200 Ω max.
Current Consumption: 21 mA max.
Warm Up Time: 30 minutes.
Electrical Connections: Screw-type terminal block.
Process Connections: Barbed, dual size to fit 1/8˝ & 3/16˝ (3 mm & 5
mm) ID rubber or vinyl tubing.
Enclosure Rating: NEMA 1 (IP20).
Mounting Orientation: Position insensitive.
Weight: 1.8 oz (51 g).
Agency Approvals: CE, RoHS

Tested to the following standards:

IEC 61000-4-2: 2008
IEC 61000-4-3: 2006
IEC 61000-4-4: 2004
IEC 61000-4-5: 2005
IEC 61000-4-6: 2006

CENELEC EN 61000-6-2: 2005
CENELEC EN 61000-6-4: 2007

CENELEC EN 55011: 2007
FCC Part 15 CFR Title 47: 2009
ICES-003: 2004 Digital Apparatus (Industry Canada)

ANSI C63.4-2003: 2003

CENELEC EN 61326-1: 2006
2004/108/EC EMC Directive

The Series 616KD One-Touch

®

Differential Pressure Transmitter

senses the pressure of air and compatible gases and sends a standard
4 to 20 mA or optional voltage output signal. A wide range of models are
available factory calibrated to specific ranges. A single push button
properly adjusts both zero and span. New enclosure enables the 616KD
to be mounted on a 35 mm DIN rail either via its side or back DIN rail
clips.

INSTALLATION
Select a clean, dry mounting location free from excess vibration.
Distance from the receiver is limited only by total loop resistance. See
Electrical Connections below. The tubing supplying pressure to the
instrument can be practically any length required, but long lengths will
increase response time slightly.

Pressure Connections
Two integral barbed tubing connections are provided. They are dual-
sized to fit both 1/8˝ and 3/16˝ (3.12 and 4.76 mm) ID tubing. Be sure the
pressure rating of the tubing exceeds that of the operating ranges.

ELECTRICAL CONNECTIONS

Shielding cabling is required. Cable shield must be attached to a reliable
earth ground. Electrical connections are made to the terminal block
located on the top of the transmitter. Terminals are marked 1, 2, 3, 4.
Determine which of the following circuit drawings applies to your
application and wire accordingly.

Wire Length
The maximum length of wire connecting transmitter and receiver is a
function of wire size and receiver resistance. Wiring should not
contribute more than 10% of the receiver resistance to total loop
resistance.

Do not exceed specified supply voltage ratings. Permanent
damage not covered by warranty will result. This unit is not

designed for 120 or 240 volts AC line operation.

CAUTION