TROUBLESHOOTING GUIDE
Trouble
Remedy
No LCD Display
• Check battery voltage Should be 1 5V DC Replace if low or bad
No Rate or Total
Displayed
• Check connection from meter pickup to display input terminals
• Check turbine meter rotor for debris Rotor should spin freely
• Check programming of flow monitor
Flow Rate Display
Interprets Reading
Constantly
• This is usually an indication of external noise Keep all AC wires separate from DC wires
• Check for large motors close to the meter pickup
• Check for radio antenna in close proximity
• Try disconnecting the pickup from the monitor pig tail This should stop the noise
Flow Rate Indicator
Bounces
• This usually indicates a weak signal Replace pickup and/or check all connections
• Examine K factor
DEFAULT K FACTOR VALUES
Meter Size
Default K factor
Lower Limit
Upper Limit
0 375
20,000
16,000
24,000
0 500
13,000
10,400
15,600
0 750
2750
2200
3300
0 875
2686
2148
3223
1 000
870 0
696 0
1044
1 500
330 0
264 0
396 0
2 000
52 0
41 6
62 0
3 000
57 0
45 6
68 0
4 000
29 0
23 2
35 0
6 000
7 0
5 6
8 0
8 000
3 0
2 4
4 0
10 000
1 6
1 3
2 0