Electrical data, Interconnecting wiring, General specification – Airedale Air Cooled Condensers R407C User Manual
Page 10

C11-45 / CS50 - 105
CONDENSERS
10
Condensers
Installation and Maintenance Manual: 6259642 V1.2.0 02/2013
General Specification
ELECTRICAL DATA
C11HI
C15HI
C20HI
C25HI
C35HI
Unit Data
(1)
Nominal Run Amps
A
0.65
1.3
2.8
2.8
2.8
Maximum Start Amps
A
2.6
5.2
5.6
5.6
5.6
Recommended Mains Fuse
A
10
10
10
10
10
Max Mains Cable Incoming
mm²
10
10
10
10
10
Mains Supply
230V / 1Ph + N / 50Hz
Fan - Per Fan
Quantity
1
2
1
1
1
Motor Size
kW
0.15
0.15
0.59
0.59
0.59
Full Load Amps
A
0.65
0.65
2.8
2.8
2.8
Locked Rotor Amps
A
2.6
2.6
5.6
5.6
5.6
OPTIONAL EXTRAS
Short Case Axial Fan - Per Fan
Quantity
1
2
1
1
1
Motor Size
kW
0.61
0.61
1.4
1.4
1.4
Full Load Amps
A
2.8
2.8
6.0
6.0
6.0
Locked Rotor Amps
A
7
7
18
18
18
Recommended Mains Fuse
A
10
10
10
10
10
EC Fans
Quantity
N/A
N/A
N/A
N/A
N/A
Motor Size
kW
N/A
N/A
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
N/A
N/A
Recommended Mains Fuse
A
N/A
N/A
N/A
N/A
N/A
C45HI
CS50
CS65
CS80
CS105
Unit Data
(1)
Nominal Run Amps
A
5.6
5.24
5.24
7.86
7.86
Maximum Start Amps
A
11.2
18.34
18.34
27.51
27.51
Recommended Mains Fuse
A
10
10
10
16
16
Max Mains Cable Incoming
mm²
10
6
6
6
6
Mains Supply
230V / 1Ph + N / 50Hz
Fan - Per Fan
Quantity
2
2
2
3
3
Motor Size
kW
0.59
0.6
0.6
0.6
0.6
Full Load Amps
A
2.8
2.62
2.62
2.62
2.62
Locked Rotor Amps
A
5.6
9.17
9.17
9.17
9.17
OPTIONAL EXTRAS
Short Case Axial Fan - Per Fan
Quantity
2
2
2
3
3
Motor Size
kW
1.4
1.4
1.4
1.4
1.4
Full Load Amps
A
6.0
6.0
6.0
6.0
6.0
Locked Rotor Amps
A
18.0
18.0
18.0
18.0
18.0
Recommended Mains Fuse
16
16
16
25
25
EC Fans
Quantity
N/A
2
2
3
3
Motor Size
kW
N/A
0.72
0.72
0.72
0.72
Full Load Amps
A
N/A
3.2
3.2
3.2
3.2
Recommended Mains Fuse
N/A
10
10
16
16
(1)
Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.
INTERCONNECTING WIRING
C11 - 45
L1
Mains Incoming 230V / 1Ph + N / 50Hz
N
E
CS50 - 105
L1
Mains Incoming 230V / 1Ph + N / 50Hz
N
PE