Chillers optichill, General description – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 9

Chillers
OPTICHILL
Chillers
9
Installation & Maintenance : 6564868 02/2013
General Description
STANDARD FEATURES
Controls
As standard, the
microprocessor controller can provide 8 stages of
capacity control.
Optionally, the controller is designed to provide capabilities for;
Building Management Systems (BMS)
Sequencing (Master/Slave and Run/Standby)
to meet all your system requirements, please specify at order.
Unit initial set up details can be found in the
CAUTION
When adding to an existing network, please consult Airedale to ensure
strategy compatibility.
Electrical
A weatherproof electrical power and controls panel is situated at the end of the unit
and contains:
Individual mains power compartments for each
refrigeration circuit
refer to
Separate door locking electrical isolation for each
mains compartment
Dedicated bus-bar chamber for connection of incoming 3-
phase and earth mains power supply
Emergency Stop fitted to controls compartment door
Separate, fully accessible, controls compartment, allowing adjustment of control set
points whilst the unit is operational
Circuit breakers for protection of all major unit components
Phase rotation relay incorporating phase loss protection (compressor module)
CAUTION
A fused and isolated electrical supply of the appropriate phase, frequency and
voltage should be installed.
The electrical power and control panel is wired to the latest European standards and
codes of practice.
Mains supply is 3 phase and a neutral is not required, refer to
Separate 230V permanent supply is required for the controls and safety features.
Electrical terminals for external evaporator pipework trace heating (230V/500W)
are provided.