Maintenance
CAUTION
ALL work MUST be carried out by technically trained competent personnel.
WARNING
The equipment contains live electrical and moving parts, ISOLATE prior to
maintenance or repair work.
The unit isolators DO NOT isolate the incoming mains supply, but isolate the
individual electrical panels. Isolate REMOTELY the mains incoming supply to the
BUSBAR chamber prior to maintenance or repair work.
The door interlocking MCCB should be in the OFF position and the auxiliary alarm
contact from the MCCB should be linked out.
WARNING
Power Factor Correction - Optional Extra
Allow Discharge time and short circuit the capacitor before handling! This applies
to any flying leads directly attached to the capacitor terminals.
IMPORTANT
UK MAINLAND - The Chiller Maintenance Record and supporting maintenance
documents MUST be complete and available on request to validate warranty.
The Chiller Maintenance Record is located within the unit control panel.
IMPORTANT
Ensure relevant F-Gas Regulation checks are carried out at the appropriate period.