Water system, Grooved & clamped type connection, Chillers optichill – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 23: Installation data

Chillers
OPTICHILL
Chillers
23
Installation & Maintenance : 6564868 02/2013
Installation Data
WATER SYSTEM
Chilled water pipework and ancillary components must be installed in accordance with:
National and Local Water supply company standards
The manufacturer's instructions are followed when fitting ancillary components
The system liquid is treated to prevent corrosion and algae forming
In ambients of 0°C and below, where static water can be expected, or when water
supply temperatures of +5°C or below is required, the necessary concentration of
Glycol or use of an electrical trace heater must be included
The schematic is referred to as a guide to ancillary recommendations
CAUTION
The unit water connections are NOT designed to support external pipework,
pipework MUST be supported separately.
GROOVED & CLAMPED
TYPE CONNECTION
1
Place Grooved Ends Together
2
Locate Rubber Gasket
Note that an expansion gap of 5mm is
shown here
The gasket should be checked for
compatability and damage prior
to installation
A thin coat of sealing lubricant should
be applied to both the inside and
outside mating surfaces
Slip the gasket fully onto one of the
pipe ends, align the second pipe and
slide the gasket into place
3
Place Clamp over Gasket
4
Secure Clamp
Wrap the 2-halves of the clamp over
the gasket
Ensure the gasket fits snugly within the
grooved recess within the inside of the
clamp and that the clamp
mates correctly
Tightend the bolts incrementally and
evenly at both sides until a leak free
seal is formed
The gasket should not be visible
beneath the clamp when the bolts are
properly tightened