Unit operating parameters, Easicool™ ezre precision air conditioning, Ope ra tion – Airedale EasiCool 6kW 64kW User Manual
Page 14

EasiCool™ EZRE
Precision Air Conditioning
14
EasiCool EZRE Operational Manual 7610207 V1.0.0_02_2013
O
pe
ra
tion
Unit Operating Parameters
Inputs and outputs can be located by the labels to the microprocessor controller.
Analogue Inputs
X/WX Unit
CW Unit
B1
Return air humidity
B1
Return air humidity
B2
Condensing Pressure
B2
Supply Air Temperature
B3
Coil Temperature
B3
Coil Temperature
B4
Not Used
B4
Not used
B5
Return Air Temperature
B5
Return air temperature
B6
Not Used
B6
Not used
Digital Inputs
ID1
Remote on/off
ID1
Remote on/off
ID2
Airflow differential pressure switch
ID2
Airflow differential pressure switch
ID3
Critical Alarm
ID3
Critical Alarm
ID4
Overheat cut-out
ID4
Overheat cut-out
ID5
Not Used
ID5
Not used
ID6
Low pressure safety switch
ID6
Not used
ID7
Compressor 1 status alarm
ID7
Not used
ID8
Compressor 2 status alarm
ID8
Not used
Analogue Outputs
Y1
Main Fan Speed Controller
Option 2 / EC Fans
Y1
Main Fan Speed Controller
Option 2 / EC Fans
Y2
Thyristor Heating
Y2
Thyristor Heating
Y3
Main Fan Speed Controller Option 1
Y3
Main Fan Speed Controller Option 1
Y4
Condenser Fan Speed Controller
Y4
Chilled Water Valve
Digital Outputs
NO1
Compressor 1
NO1
Open CW Valve
NO2
Compressor 2
NO2
Close CW Valve
NO3
Not Used
NO3
Not Used
NO4
HGRH / Heat Stage 1 / LPHW Valve Open
NO4
Heat Stage 1 / Open LPHW Valve
NO5
Heat Stage 2 / LPHW Valve Close
NO5
Heat Stage 2 / Close LPHW Valve
NO6
Heat Stage 3
NO6
Heat Stage 3
NO7
Not Used
NO7
Not Used
NO8
Common Alarm
NO8
Common Alarm
CAUTION
Inputs or outputs not required will not be connected nor will they appear on the display keypad.
SERVICE INDICATOR
The maintenance of key components such as compressors, fans and air filters can be monitored via a service indicator
which visually demonstrates the status relative to the component service intervals.
Inputs and outputs can be located by the labels to the microprocessor controller.