Page 80: Performance data, Operating limits

EasiCool™
Precision Air Conditioning
Technical Data Upflow
Performance Data
Cooling Capacity (1)
Chilled Water Inlet/Outlet °C
Air On
5/10°C
7/12°C
8/14°C
10/16°C
(DB°C/%RH)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
V6CW-EZRE
22/50
8.2
6.6
6.2
5.8
5.0
5.0
3.9
3.9
24/45
9.7
7.9
7.6
7.0
6.2
6.2
5.2
5.2
26/40
11.1
9.3
8.9
8.3
7.5
7.5
6.5
6.5
V8CW-EZRE
22/50
10.6
8.6
8.0
7.5
6.4
6.4
5.1
5.1
24/45
12.4
10.1
9.7
8.9
7.9
7.9
6.7
6.7
26/40
14.0
11.7
11.2
10.5
9.5
9.5
8.2
8.2
V10CW-EZRE
22/50
12.7
10.3
9.6
9.0
7.7
7.7
6.1
6.1
24/45
14.8
12.1
11.7
10.7
9.5
9.5
8.0
8.0
26/40
16.8
14.0
13.5
12.6
11.4
11.4
9.8
9.8
V13CW-EZRE
22/50
15.6
12.4
11.9
10.8
9.4
9.4
7.5
7.5
24/45
18.4
14.8
14.7
13.2
11.8
11.8
9.9
9.9
26/40
21.2
17.4
17.2
15.7
14.3
14.3
12.4
12.4
V15CW-EZRE
22/50
18.5
14.7
14.1
12.8
11.1
11.1
8.9
8.9
24/45
21.5
17.3
17.1
15.3
13.7
13.7
11.5
11.5
26/40
24.3
20.0
19.8
18.0
16.4
16.4
14.2
14.2
V17CW-EZRE
22/50
20.8
16.6
15.9
14.4
12.5
12.5
10.0
10.0
24/45
24.2
19.5
19.2
17.3
15.5
15.5
13.0
13.0
26/40
27.4
22.5
22.3
20.3
18.5
18.5
16.0
16.0
V20CW-EZRE
22/50
23.5
18.8
17.9
16.4
14.2
14.2
11.3
11.3
24/45
27.6
22.3
21.8
19.8
17.7
17.7
14.9
14.9
26/40
31.4
26.0
25.5
23.5
21.3
21.3
18.4
18.4
V22CW-EZRE
22/50
25.3
20.5
18.7
16.9
15.5
15.5
12.4
12.4
24/45
29.7
24.3
23.4
21.6
19.2
19.2
16.1
16.1
26/40
33.8
28.3
26.5
24.1
23.1
23.1
20.0
20.0
V26CW-EZRE
22/50
29.2
23.7
21.6
19.5
17.8
17.8
14.3
14.3
24/45
34.1
27.9
26.9
24.8
22.1
22.1
18.5
18.5
26/40
38.7
32.4
30.5
27.6
26.5
26.5
22.9
22.9
V28CW-EZRE
22/50
36.9
29.1
28.6
25.5
22.5
22.5
18.3
18.3
24/45
42.7
34.2
34.2
30.5
27.5
27.5
23.2
23.2
26/40
48.1
39.5
39.3
35.7
32.7
32.7
28.4
28.4
TC = Total Cooling SC = Sensible Cooling
(1)
All data quoted is gross.
(2)
Deduct fan motor gain for nett duties, refer to
Mechanical Data
.
(3)
Water flow rate (l/s) = TC ÷ (4.19 x ∆T) at 100% Water. For glycol use, refer to
Ethylene Glycol Correction Factors
.
(4)
Refer to
Waterside Pressure Drop (kPa)
.
Operating Limits
Indoor Air Temperature
+18°C to +28°C
Indoor RH%
+40% to +55%
Water Entering Temperature
+5°C to +10°C
Water Leaving Temperature
+10°C to +16°C
(1)
Conditions quoted at 100% Water.
(2)
For conditions outside those quoted, please refer to Airedale.
80
EasiCool Technical Manual 7535768 V1.2.0_02_2013