Easicool™ precision air conditioning, Mechanical data v40cw – Airedale EasiCool 6kW 64kW User Manual
Page 108

EasiCool™
Precision Air Conditioning
V40CW-EZRE-0
V40CW-EZRE-1
V40CW-EZRE-2
Capacity
Nom Cooling (Gross)
(1)
kW
47.6
47.6
47.6
Fan Power Input (Fan Gain)
(2)
kW
6.30
6.30
6.30
Dimensions
W x D x H
mm
1835 x 750 x 1940
1835 x 750 x 1940
1835 x 750 x 1940
Weight
Machine
(3)
kg
429
429
429
Construction
Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour
Frame: Aluminium Frame with Aluminium Corners
Cooling Coil
Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages
1 (Modulated) / 1
Evaporator Fan Motor - AC Motor
Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type
Belt and Pulley
Quantity
1
1
1
Motor Shaft Power
(4)
kW
5.5
5.5
5.5
Speed @ 25Pa / Maximum ESP
rpm
1620 / 1622
1620 / 1622
1620 / 1622
Maximum ESP
Pa
25
25
25
Nominal Airflow
m³/s
3.7
3.7
3.7
Connections
Inlet/Outlet
mm
42
42
42
Condensate Drain Hose
mm
19
19
19
Filtration
Disposable to BS EN 779 - G4 - 75mm
Quantity
4
4
4
OPTIONAL EXTRAS
Electric Heating (Total)
kW
30
30
30
Humidifier
Capacity
kg/hr
3.0 - 15.0
3.0 - 15.0
3.0 - 15.0
Feed/Drain
3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head
m
10.8
10.8
10.8
Flow
l/m
5
5
5
Drain
10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor
Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type
Belt and Pulley
Quantity
N/A
N/A
N/A
Motor Shaft Power
(4)
kW
N/A
N/A
N/A
Speed @ Maximum ESP
rpm
N/A
N/A
N/A
Maximum ESP
Pa
N/A
N/A
N/A
Fan Power Input (Fan Gain)
(2)
kW
N/A
N/A
N/A
Optional Fan - EC Motor
Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type
Direct Drive
Quantity
2
2
2
Motor Shaft Power
(4)
kW
N/A
N/A
N/A
Speed @ 25Pa / Maximum ESP
rpm
2165 / 2165
2165 / 2165
2165 / 2165
Maximum ESP
Pa
25
25
25
Fan Power Input (Fan Gain)
(2)
kW
4.24
4.24
4.24
Larger Fan Motor - AC Motor
Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size
(4)
kW
N/A
N/A
N/A
Speed @ Maximum ESP
rpm
N/A
N/A
N/A
Maximum ESP
Pa
N/A
N/A
N/A
Fan Power Input (Fan Gain)
(2)
kW
N/A
N/A
N/A
Low Pressure Hot Water
Copper Tube/Aluminium Fin
Capacity Gross
(5)
kW
31.5
31.5
31.5
Water Flow (Nominal)
l/s
0.70
0.70
0.70
LPHW Connection Sizes
mm
22
22
22
Threaded Connections
Brass Male Taper
in
1 1/2
1 1/2
1 1/2
108
EasiCool Technical Manual 7535768 V1.2.0_02_2013
Te
ch
ni
ca
l
Chi
lle
d W
at
er
V
Technical Data Upflow
Mechanical Data
V40CW