Precision Air Conditioning
Technical Data
●
Nominal Design Operating Condition 24°C Dry Bulb 45% RH
IMPORTANT
Fan Power Input (Fan Gain) must be added to the room load to establish full gross cooling capacity requirements.
Fan Power Input can be found in the mechanical data sections.
Fan Power Input is taken at the operating conditions based on 25Pa ESP.
Te
ch
nic
al
39
EasiCool Technical Manual 7535768 V1.2.0_02_2013
Chi
lle
d W
ate
r
DF
Operating Limits
Indoor Air Temperature
+18°C to +28°C
Indoor RH%
+40% to +55% (Based upon 24°C Dry Bulb)
Water Entering Temperature
+5°C to +10°C
Water Leaving Temperature
+10°C to +16°C
Moisture Content
Operating Band