Easicool™ precision air conditioning, Dimensional & installation data, Ins ta lla tio n – Airedale EasiCool 6kW 64kW User Manual
Page 33: Minimum unit clearances, Open & enclosed floorstands option, Ec fan motor option, Minimum ceiling clearance

EasiCool™
Precision Air Conditioning
Dimensional & Installation Data
Minimum Unit Clearances
Open & Enclosed Floorstands Option
A
B
C - Floorstand(3)
Min 200 - Max 750
(+ 50mm Feet
Adjustable +/- 20mm)
D(4)
DF6 - DF10
mm
670
610
Min 300
DF13 - DF17
mm
990
610
Min 300
DF20 - DF26
mm
1310
610
Min 300
DF28 - DF31
mm
1460
700
Min 300 - Max 800
(+ 50mm Feet
Adjustable +/- 20mm)
N/A
DF35 - DF45
mm
1835
700
N/A
DF50 - DF60
mm
2170
700
N/A
EC Fan Motor Option
A
B
C (3)
D(5)
With Feet Only (4)
With Leg & Feet (4)
Min
Max
Min
Max
DF6 - DF10
mm
670
610
284
329
604
1074
Min 300
DF13 - DF17
mm
990
610
362
407
697
1152
Min 300
DF20 - DF26
mm
1310
610
362
407
697
1152
Min 300
DF28 - DF31
mm
1460
700
356
401
686
1146
Min 300
DF35 - DF45
mm
1835
700
356
401
686
1146
Min 300
DF50 - DF60
mm
2170
700
356
401
686
1146
Min 300
Minimum Ceiling Clearance
E
Forward Only
Forward & 1 Side
Forward & 2 Sides
All Faces
DF6 - DF10
mm
470
240
160
120
DF13 - DF17
mm
550
330
240
170
DF20 - DF26
mm
560
370
280
190
DF28 - DF31
mm
620
410
310
210
DF35 - DF45
mm
640
450
350
230
DF50 - DF60
mm
640
480
380
240
(1)
Shown with optional open floor stand.
(2)
Shaded area indicates minimum service and maintenance requirements.
(3)
Dimension C denotes recommended minimum/maximum floorstand height, refer to Airedale for special applications, please specify at order.
(4)
Min = Threaded foot at minimum extension.
Max = Threaded foot at maximum extension.
(5)
Dimension D refers to units fitted with LPHW which require access to the RHS of the unit to set up the regulating valve.
(6)
SERVICES SIDE ACCESS GLAND PLATE, OPTIONAL POSITION; ensure appropriate clearance is available to the base of the RHS of the unit if this option is
selected.
33
EasiCool Technical Manual 7535768 V1.2.0_02_2013