Easicool™ precision air conditioning, Ins ta lla tio n – Airedale EasiCool 6kW 64kW User Manual
Page 37

EasiCool™
Precision Air Conditioning
Interconnecting Wiring
L1
L2
INDOOR UNIT
L3
N
PE
Mains Incoming Supply
400V / 3PH + N / 50Hz
560
Common Alarm Normally Open
561
Common
562
Common Alarm Normally Closed
INDOOR UNIT
583
Fire Detection
502
24Vac
560
Non-Critical Alarm Normally Open
561
Common
562
Non-Critical Alarm Normally Closed
563
Critical Alarm Normally Open
INDOOR UNIT
564
Common
565
Critical Alarm Normally Closed
583
Fire Detection
502
24Vac
522
Remote On/Off
502
24Vac
Rx-Tx-
Rx+Tx+
GND
Rx-Tx-
Rx+Tx+
GND
INDOOR UNIT
Network Connections (Inward connection)
Network Connections (Outward connection)
INDOOR UNIT
CW Models
Sizes 6-26
Sizes 28-60
Remote On / Off
Network
37
EasiCool Technical Manual 7535768 V1.2.0_02_2013
Ins
ta
lla
tio
n