Page 57: Electrical data df20cw

EasiCool™
Precision Air Conditioning
57
EasiCool Technical Manual 7535768 V1.2.0_02_2013
Te
ch
nic
al
Chi
lle
d W
ate
r
DF
DF20CW-EZRE-0
DF20CW-EZRE-1
DF20CW-EZRE-2
Unit Data Full Function
(1)
Nominal Run Amps
A
29.7
35.3
63.5
Maximum Start Amps
A
29.7
35.3
63.5
Recommended Mains Fuse Size
A
40
50
80
Unit Data Cooling Only
Nominal Run Amps
(2)
A
4.8
9.1
18.2
Maximum Start Amps
A
4.8
22.8
45.5
Recommended Mains Fuse Size
A
10
16
25
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50HZ
380V / 3PH + N / 60HZ
220V / 3PH / 60HZ
Control Circuit
VAC
24
24
24
Evaporator Fan Motor - Per Fan
Centrifugal Forward Curved DD EC - Designed to 25Pa ESP
Motor Type
EC
AC
AC
Maximum Electrical Input Power
(3)
kW
2 x 1.15
2 x 0.6
2 x 0.6
Full Load Amps
A
4.8
9.1
9.1
Locked Rotor Amps
A
4.8
22.75
22.75
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
2
2
2
Number of Elements
6
6
6
Rating
kW
15
15
15
Current per Phase
A
21.65
22.79
39.36
Humidifer
Capacity
kg/hr
3
3
3
Rating
kW
2.25
2.25
2.25
Full Load Amps
A
3.25
3.42
5.90
Evaporator Fan Options
Larger Fan Motor - Per Fan
Maximum Electrical Input Power
(3)
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Standard Size Motor - EC Motor - Per Fan
Centrifugal Backward Curved DD EC - Designed to 25Pa ESP
Maximum Electrical Input Power
(3)
kW
1 x 2.55
1 x 2.55
1 x 2.55
Full Load Amps
A
3.9
3.9
3.9
Technical Data Downflow
Electrical Data
DF20CW
Mechanical
(1)
Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2)
Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3)
With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4)
Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5)
Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to
Low Pressure Hot Water (Optional Extra) - X & WX Models
.
Electrical
(1)
Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2)
Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3)
Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.