beautypg.com

Advanced Protection HPS User Manual

Page 5

background image

5

SPDs for ungrounded systems can be installed on grounded

systems with a clamping performance penalty. However, SPDs

for grounded systems installed on ungrounded systems are

almost certainly destined for premature failure. Call APT Tech

Support at (800) 237-4567 for further information.

Circuit Breaker and Disconnect Switch

This HP and HPS SPDs are tested and qualified as

Type 2 SPDs per UL 1449 Third Edition and 2008 NEC

®

.

This SPD can be installed on the load side of the service

overcurrent device per 2008 NEC

®

Article 285.

When connected on load side of main disconnect, we suggest

connecting via a 60A circuit breaker. The circuit breaker is

the intended disconnect switch and provides short circuit

protection to the connecting conductors. The HP and HPS

Series have internal overload protection elements within

the product. A breaker or disconnect is not required for the

SPD’s overcurrent protection. HP and HPS SPDs have

demonstrated 200kA Short Circuit Current Ratings (SCCR).

Confer to label on unit.

Terminals

Terminals will accept 14 - 2 AWG conductor and are provided

for line (phase), neutral (if used), and equipment safety ground

connections. 8 AWG is the minimum recommended wire size

because UL testing and evaluation was performed using 8 AWG.

Wire Size and Installation Torque

This is a parallel-connected SPD; it is not series-connected.

The size of the SPD wiring is independent of the ampere

rating of the protected circuit. Recommended wire is 6

AWG for phase, neutral and ground connections. Torque

connections to 18 inch-pounds. Conductor length should

be as short as possible.

If other wire sizes are used, we recommend that all

conductors be the same gauge. Note that larger conductor

might appear to be beneficial; however, it tends to have

the same inductance as smaller conductor and is more

difficult to work with.

Terminals accept 14 - 2 AWG conductor with 6 AWG being

preferred. Coordinate conductor size and overcurrent

protection per applicable codes.

System Grounding

An equipment grounding conductor must be used on

all electrical circuits connected to the SPD. For the best

performance, use a single point ground system where the

service entrance grounding electrode system is connected

to and bonded to all other available electrodes, building

steel, metal water pipes, driven rods, etc. (for reference

see: IEEE Std 142-2007).

For sensitive electronics and computer systems, we

recommend that the ground impedance measurement be

as low as possible. When metallic raceway is used as an

additional grounding conductor, an insulated grounding

conductor should be run inside the raceway and sized per

the NEC

®

. Adequate electrical continuity must be maintained

at all raceway connections. Do not use isolating bushings

to interrupt a metallic raceway run.

A separate isolated ground for the SPD is NOT

recommended. Proper equipment connections to grounding

system and ground grid continuity should be verified via

inspections and testing on a regular basis as part of a

comprehensive electrical maintenance program.

On 4-Wire Power Systems, neutral to ground bonding (Main

Bonding Jumper) must be installed per the NEC

®

. Failure

to do so WILL damage SPDs.

Internal Mounting of XR and XW Component SPD

XTE versions of the HP and HPS families are essentially

TE/HPSs without enclosures. XTE/HPs and XTE/HPSs are

intended for installation within host electrical equipment

having suitable enclosures.

The experienced integrator will appreciate the simplicity

of XTE/HP and XTE/HPS. XTE/HP and XTE/HPS are

Type 4 SPDs that have been evaluated by UL for use as

Type 2 SPDs when installed in appropriate enclosures.

All UL required safety testing is complete without needing

additional safety apparatus. Contact factory for UL file

Engineering Considerations. Mount SPD in appropriate

enclosure, mount Diagnostic Display in appropriate location

and follow appropriate instructions including short leads. UL

evaluation within your completed product should be easy

and trouble free. Do not Hi-Pot test with SPD in circuit.

In many instances, a disconnecting means is appropriate

for future service. A breaker serves this function, as well

as provides overcurrent protection to the connecting

conductors. If a breaker is not used, consider a disconnect

or safety switch having appropriate SCCR rating including

any required overcurrent protection. Please contact APT

Technical Support as appropriate.

Mounting Diagnostic Display: Mount Display in a user

friendly location, with considerations to weather and

vandalism. Dimensions are in Table 2. A Display with a

6’ connector cable is typically included. Longer lengths

are available. The Display features a UL 94-5VA and UL

746C(f1) polymeric label. A gasket is included. This same

display & gasket are used in the TE/HP and TE/HPS

series and UL has Listed them with an enclosure rating

of Type 1/12/3R/4.

UL 1283 required language concerning the installation

of EMI Filters

a) An insulated grounding conductor that is identical in size

and insulation material and thickness to the grounded and

ungrounded circuit supply conductors, except that it is green

with or without one or more yellow stripes, is to be installed

as part of the circuit that supplies the filter. Reference should

be made to Table 250-122 of the National Electrical Code

regarding the appropriate size of the grounding conductor.

b) The grounding conductor mentioned in item “a” is to

be grounded to earth at the service equipment or other

acceptable building earth ground such as the building frame

in the case of a high-rise steel-frame structure.

c) Any attachment-plug receptacles in the vicinity of the

filter are to be of a grounding type, and the grounding

conductors serving these receptacles are to be connected

to earth ground at the service equipment or other acceptable

building earth ground such as the building frame in the case

of a high-rise steel-frame structure.

d) Pressure terminal or pressure splicing connectors and

soldering lugs used in the installation of the filter shall be

identified as being suitable for the material of the conductors.

Conductors of dissimilar metals shall not be intermixed in a

terminal or splicing connector where physical contact occurs

between dissimilar conductors unless the device is identified

for the purpose and conditions of use.

This manual is related to the following products: