beautypg.com

Figura 8 planos eléctricos para conexiones típicas, Te/1hp, Te/3hp – Advanced Protection HPS User Manual

Page 19: Te/5hp, te/9hp, Te/2hp, te/4hp, te/7hp, te/8hp

background image

7

Figura 8

PLANOS ELÉCTRICOS PARA CONEXIONES TÍPICAS

TE/1HP

SPLIT

2 Hots, 1 Neu, 1 Grnd

Hot (BLK)

Hot (BLK)

Neutral (WHT)

V

V

}

}

Ground (GRN)

TE/3HP

HI-LEG DELTA (B High)

3 Hots, (B HIGH),

1 Neu, 1 Grnd

Phase A (BLK)

Phase B (ORNG)

Neutral (WHT)

Phase C (BLK)

Ground (GRN)

}

V

TE/51HP, TE/61HP, TE/91HP

CORNER GROUND

DELTA (B grounded)

2 Hots, 1 Grnd

Phase A (BLK)

Phase C (BLK)

Ground (GRN)

V

}

TE/5HP, TE/9HP

Phase A (BLK)

Phase C (BLK)

Phase B (BLK)

Ground (GRN)

V

}

DELTA & HRG WYE

3 Hots, 1 Grnd

TE/2HP, TE/4HP, TE/7HP, TE/8HP

WYE

3 Hots, 1 Neu, 1 Grnd

}

Phase A (BLK)

Phase B (BLK)

Neutral (WHT)

Phase C (BLK)
Ground (GRN)

A

C

N

V

B

This manual is related to the following products: