4electrical connection, 1 terminals – West Control Solutions KS 816 User Manual
Page 9
![background image](/manuals/370865/9/background.png)
9499 040 55811
Multiple transmitter and temperature controller KS 816
9
4
Electrical connection
• The max. permissible voltage against ground of the input and signal leads is 50
Veff.
• Power supply leads must be kept separate from signal and input leads.
• For output protection and interference suppression, connected contactors must
be provided with protective circuitry to manufacturer specifications.
4.1 Terminals
All terminals leading to the process are designed as (plug-in type) screw or
screwless spring-clamp terminals.
The terminals are not delivered with the unit and must be ordered separately.
Make: PHOENIX COMBICON
Two types are available:
Screw terminal
5 x FRONT-MSTB 2,5/18-ST-5,08
1 x FRONT-MSTB 2,5/8-ST-5,08
PMA order no.
9407 799 00001
9407 799 00011
Spring-clamp terminal
5 x FK-MSTBP 1,5/18-ST-5,08
8-pole only screw terminals
PMA order no.
- - - - - -
- - - - - -
Note: The spring-clamp terminals are shown in the KS 816 figures. These have a
separate "test socket".
With screw terminals, the screw heads are used for test measurements.
Connecting capacity
FRONT-MTSB 2,5/...-ST
FK-MSTBP 1,5/...-ST
rigid
flexible
1
)
rigid
flexible
1
)
One conductor
0,2 - 2,5
0,25 - 2,5
0,2.- 1,5
0,25 - 1,5
Several conductors [mm
2
]
2
)
0,2 - 1,5
0,25 - 1,0
0,2 - 1,0
0,5 - 0,75
3
)
1
) with end crimps
2
) 2 conductors of equal cross-section
3
) with TWIN end crimps
Make: WAGO multi-connector system MIDI
Spring-clamp terminal
5 x connector strip CAGE CLAMP connection
WAGO-order-no. 231-318/026-000
PMA-order-no. 9463 000 05341
1 x connector strip with CAGE CLAMP connection
WAGO-order-no. 231-308/026-000
PMA-order-no. 9463 000 05321
Connecting capacity
only one conductor: 0,08 - 2,5 mm
2
, single-wire,
multi-wire, fine wire,
end crimp, cable shoe