beautypg.com

West Control Solutions KS 816 User Manual

Page 10

background image

10

9499 040 55811

Multiple transmitter and temperature controller KS 816

Galvanic isolations

The KS 816 galvanic isolations are shown below:
Identical block shading means that the blocks are galvanically connected. (All in-
puts are galvanically connected.)

4.3 Power supply

KS 816 is designed for 24V DC nominal supply voltage, range 18V to 30V, 5%
ripple. The supply voltage must meet the conditions for protective low voltage
(SELV) to CEI 364-4-41 [VDE 0100-410].

Power supply load by one KS 816:

approx. 5 W

Energization is via terminals 7 (+) and 8 (-) of connector X3.

.

4.4 Fuses

Each unit must be protected with a separate 2A slow-blowing fuse (fitted in the ter-
minal). We recommend using terminals with built-in fuses.
Unless LED "PWR" is lit with the supply voltage applied (check fuse and polarity),
the unit is defective and must be returned to the manufacturer.