3installation – West Control Solutions KS 816 User Manual

Page 7

background image

9499 040 55811

Multiple transmitter and temperature controller KS 816

7

3

Installation

3.1 Mounting

KS 816 is provided for mounting on rails 35 x 7,5 (top-hat rail) to EN 50 022,
EN 50 035, EN 50 045.
Grounding is via a spring on the top-hat rail. Therefore, note that there must be a
good conducting connection with the grounded mounting wall (layer of lacquer in-
stead of conducting mounting wall, Eloxal, ...). If necessary, the clip-on rail must be
grounded with a separate connection.

Single unit: For mounting, pull the two lateral catches upwards by approx. 5 mm
via a stop and snap the unit onto the rail.
Press the catches down to fix the unit to the rail.

Several units: For mounting several units side by side, snap the first unit onto the
rail and lock only the side at which no further unit must be mounted. Mount the se-
cond unit accordingly, approx. 2 cm beside the first one, and connect it to the first
one by shifting it laterally (pins locked into position). Press down the second catch
of the first unit only now.