beautypg.com

Dimmer status, Reboot, Set default level time – AMX Radia Eclipse 4-Channel Dimmer Module RE-DM4 User Manual

Page 49: Set default preset time

background image

AMX RADIA Lighting Programming

41

RE-DM4 and RE-DM6 RADIA Eclipse Dimmer Modules

Dimmer Status

This function returns the status of the specified dimmer.



The use of multiple dimmers (e.g. 'A', '&', and '-') are not allowed with this function, and their use
will return an error.



If the level of the dimmer is undefined, the level is reported an 'UN'.



This is the only method used to determine if a level is undefined. For example, the response to the
command above would be: "12,'CHAN:3 CURV:1 LEV:UN',13,10,'?'"

Reboot

This function reboots the dimmer and initializes it to its power-up state. The device will go off-line with the
master and return on-line.

If is specified, it must be 1.

Set Default Level Time

This function sets the time taken for a level to change from its current level to a new level when using a level
command.

Set Default Preset Time

This function sets the time taken for a preset recall to ramp when no time is specified to override this default
time.

Dimmer Status

String:

Response:

CHAN: CURV: LEV:

Example:

SEND_STRING Radia,"'3',13"

Request dimmer 3 status

Response: "12,'CHAN:3 CURV:1 LEV:43',13,10,'?'"

Reboot

String:

[]QQQ

Response:

None

Example:

SEND_STRING Radia,"'QQQ',13"

Reboot dimmer

Response: none

Set Default Level Time

String:

LT

Response:

'LEVEL TIME SET AT

Example:

SEND_STRING Radia,"'LT3',13"

Set default level ramp time to 3 seconds

Response: "12,'LEVEL TIME SET AT 003',13,10,'?'"

SEND_STRING Radia,"'LT0',13"

Set default level ramp time to 0 seconds
(instantaneous)

Response: "12,'LEVEL TIME SET AT 000',13,10,'?'"

Set Default Preset Time

String:

PT

Response:

PRESET TIME SET AT

Example:

SEND_STRING Radia,"'PT4',13"

Set default preset ramp time to 4 seconds

Response: "12,'PRESET TIME SET AT 004',13,10,'?'"