FOR MODEL

K401Z

FOR MODEL

K601Z

FOR MODEL K801Z

1

2

3

4

5

6

7

8

COMMON

MOMENTARY PUSHBUTTON

(One required for each circuit)

23

TORK K-SEASONAL

DIGITAL TIME SWITCHES & ENERGY MANAGEMENT CONTROLS

REMOTE SWITCHED OVERRIDES

TRANSFORMER RELAY POWERPACK (TRP) ACCESSORY

FIG. 6

FIG. 5

SINGLE CIRCUIT CONTROL

CAUTION!

DO NOT APPLY VOLTAGE
TO THESE TERMINALS

APPLICATION:

For direct control by TORK digital
time switches or lower amperage
mechanical time switches where
switching of higher load capacity
is necessary. For example,
1.0 HP exhaust fan is switched
by a TORK controller using
simple low voltage wire.

TORK DIGITAL CONTROL

TERMINAL BLOCK

NO

C

NC

1.0 HP

MOTOR

WHITE

LOAD

N

BLACK

RED

RED

L

BLACK

RED

BLUE

TORK

TRP

NOT

USED

BLUE

RED

SWITCHING CAPACITY — TRP SERIES

20A Ballast

TRP 1 — 120VAC input

20A Tungsten (at 120VAC)

TRP 2 — 277VAC input

General Use

TRP 5 — 230VAC input

1.0 HP at 120VAC
1.5 HP at 230/277VAC

Choose the correct TRP for each load