KYORITSU 6201A User Manual
Page 24

— 22 —
• When the function is set to extension leads test while pressing Select
switch, Power on leakage current test will be carried out instead of
Insulation resistance test.
・ Protective conductor resistance between accessible conductive parts and
connection of protective earth.
・ Leakage Current test: Measure a leakage current by actually operating
the appliance.
Extension Leads Test (Select the Leakage current test) Flowchart
Start
#
CAUTION
• When the terminal is open or the resistance value exceeds measuring
range, “OL” mark (over range display) appears on the LCD.
• The test will stop. A message “Stp” appears on the LCD but values of
Leakage current aren't displayed.
(1). Protective conductor resistance test.
RPE <
= 1Ω?
(2). Power on Leakage current test
LEA <
= 1mA?
Light up in red
“
no” →“Con”→“value” will
be repeated on the LCD.
Light up in red
Stop the test and
“
no” →“LEA”→“value” will
be repeated on the LCD.
Value of (1). and (2). will be
alternately displayed on the LCD.
No
No
Yes
Yes
PASS
Light up in green
Light up in green
Brief indications“S-”and“on”will be displayed
in turns on the LCD for 5 sec and prompt the
user to set the DUT switch on.
Then a mark indicating working DUT function
will be displayed for 10 sec.
5sec
10sec