KYORITSU 6010A User Manual
Page 17
― 15 ―
Fig 7
4.If the mains warning lamp lights and/or the buzzer sounds DO NOT PRESS
THE TEST BUTTON but disconnect the instrument from the circuit. Make
the circuit dead before proceeding.
Fig 8
5.Press the test button when the display will show the insulation resistance of
the circuit or the appliance to which the instrument is connected.
6.Note that if the circuit resistance is greater than 20MΩthe instrument will
automatically range to the 200MΩreading.
All fuses in or circuit
breakers closed
Mains Switch off
Equipment disconnected
Switches closed
Lamps out
E
Reading not less
than 0.5 MΩ
Main
switch
open
See also other documents in the category KYORITSU Tools: