② Slide the terminal cover to the right to disclose the OUTPUT
terminal and insert the output plug into the terminal. Make
connection to the recording device.
③ When the plug is inserted into the output terminal, auto-range
function is cleared.
Set the range depending on the state of Data Hold Switch.
Data Hold Switch OFF 400A range
Data Hold Switch ON 2000A range
Note: After measurement, be sure to return Data Hold Switch to OFF
position.
④ Set the function selector switch to the desired position (ACA or
DCA) and follow appropriate measurement instructions.
NOTE
● During current measurement, keep the transformer jaws fully
closed. Otherwise, accurate measurement cannot be made.
The maximum measurable conductor size is approx. 55mm in
diameter.
● Zero adjustment is not necessary on AC current range.
● On DC current range, the Zero Adjust/Reset button may not
completely zero adjust the output voltage from the OUTPUT
terminal. In this case, make zero adjustment on the recording device.
● Connecting the plug to the OUTPUT terminal disables the Auto-
power-off function. The function is enabled on removing the plug
from the terminal.