Station address: DIP switch positions

The station address is calculated by adding the "ON" values of each switch on the DIP switch
block. The default setting for each switch is “OFF”.

Station address

• If the "Station Address" DIP switches are set to a correct station address (≤125), the device

uses this address. The Set_Slave_Add service is not used. Automatic Ident. Number
adaptation is not possible via Set_Slave_Add service in this case. Physical block parameter
FACTORY_RESET code 2712 (reset station address to its default value) is rejected.

• If the "Station Address" DIP switches are set to an incorrect address (>125), the device

ignores this setting. The Set_Slave_Add service and the Physical block parameter
FACTORY_RESET code 2712 (reset station address to its default value) are used. If
No_add_Cfg flag is set to "ON", the device will continue to use FACTORY_RESET code 2712.

• If the "Station Address" DIP switches are changed from an incorrect address to a correct

address, the device uses the address set on the DIP switch block.

• If the "Station Address" DIP switches are changed from a correct address to an incorrect

address, the device will use the default address 126. The flag No_Add_Chg will be set back to
"OFF".

Function

Bit

DIP switch positions

Value ("OFF")

Value ("ON")

Hardware

1

7

OFF

ON

Station address

6

+ 0

+ 64

5

+ 0

+ 32

4

+ 0

+ 16

3

+ 0

+ 8

2

+ 0

+ 4

1

+ 0

+ 2

0

+ 0

+ 1

1 If this DIP switch is set to "ON", you cannot use the network bus to change the station address

INFORMATION!
You can also use the local display (menu item 2.6.1 ADDRESS) to set the Station Address to a
new value. You can change the value when the Hardware DIP switch is "OFF". If the Hardware
DIP switch is "ON", you can see the Station Address on the local display screen but you cannot