PROFIBUS PA

4

OPTIWAVE 5200 C

www.krohne.com

10/2013 - 4003066901 - MA OPTIWAVE5200C-PA-R01-en-

2.1 Software history

2.2 Device description

This device is a 2-wire level transmitter that uses FMCW (Frequency Modulated Continuous
Wave) / Radar technology. Radar is a non-contact technology. It measures the distance, level,
mass, volume, flow rate and reflection of liquids, pastes and slurries .It is particularly suitable
for the level measurement of corrosive and viscous products.

The level transmitter has an MBP (Manchester-coded, bus-powered) interface to connect the
device to a PROFIBUS PA network, when equipped with the appropriate options.

The level transmitter is approved for use in potentially explosive atmospheres when equipped
with the appropriate options.

2.3 Function blocks and the PROFIBUS PA Profile

The Analog Input Function Block agrees with PROFIBUS PA Profile 3.02. The Analog Input
Function Block is the data interface to a process control system (a PLC, ...). The control system
(cyclic communication services) can read or write input and output data.

The device has these blocks:

Issued Signal converter

Application program

System integration

Mth./
year

Hardware

Firmware

Hardware

Software

Driver

Version

Model name

08/13

PROFIBUS PA

module Ident.

No.

0x4550

(4001858601c)

V2.42.0.42

Simatic

PCS7

or

other SPS

of other

manufact.

HW Config

or

other

Software of

other SPS

manufact.

GSD (device

specific)

KR014554.GSD

OPTIWAVE

5200

GSD (profile

specific)

PA1397.GSD

AI 1 (Phy MBP)

Laptop / PC

PDM

(≥ 6.0 SP5)

DD

(Ident.-No.)

Pactware

DTM ≥

1.0.0

INFORMATION!
The PROFIBUS PA Profile 3.02 has a standard set of parameters and functions available for
PROFIBUS devices used in process control. The PROFIBUS device is a function block application
in which parameters and functions are grouped into different blocks.

Block

Usage

1 Physical Block (PB)

contains identification and diagnosis parameters of the device

1 Level Transducer Block (TB-Level)

contains parameters and functions to control the level

measurement

4 Analog Input Function Blocks (AI-FB)

contains parameters and functions to control the measuring

output; provides the measuring value(s)